Update modbus documentation to add fan state settings (core PR#104577) (#30018)
* Update modbus documentation to add fan state settings core PR incoming to add this feature * Update modbus.markdown Remove list option from fan mode values
This commit is contained in:
parent
642d2db73b
commit
1069f926d0
@ -531,7 +531,7 @@ The master configuration like device_class are automatically copied to the slave
|
||||
|
||||
## Configuring climate entities
|
||||
|
||||
The Modbus climate platform allows you to monitor a thermostat or heaters as well as set a target temperature.
|
||||
The Modbus climate platform allows you to monitor a thermostat or heaters as well as set a target temperature, HVAC mode and fan state.
|
||||
|
||||
Please refer to [Parameter usage](#parameters-usage-matrix) for conflicting parameters.
|
||||
|
||||
@ -613,7 +613,7 @@ climates:
|
||||
state_auto:
|
||||
description: "Value corresponding to HVAC Auto mode."
|
||||
required: false
|
||||
type: integer
|
||||
type: [integer, list]
|
||||
state_dry:
|
||||
description: "Value corresponding to HVAC Dry mode."
|
||||
required: false
|
||||
@ -626,6 +626,61 @@ climates:
|
||||
description: "Value corresponding to HVAC Heat/Cool mode."
|
||||
required: false
|
||||
type: [integer, list]
|
||||
fan_mode_register:
|
||||
description: "Configuration of register for Fan mode"
|
||||
required: false
|
||||
type: map
|
||||
keys:
|
||||
address:
|
||||
description: "Address of Fan mode register."
|
||||
required: true
|
||||
type: integer
|
||||
values:
|
||||
description: "Mapping between the register values and Fan modes
|
||||
This is typically used to control one of: Speed, Direction or On/Off state."
|
||||
required: true
|
||||
type: map
|
||||
keys:
|
||||
state_fan_on:
|
||||
description: "Value corresponding to Fan On mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_off:
|
||||
description: "Value corresponding to Fan Off mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_low:
|
||||
description: "Value corresponding to Fan Low mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_medium:
|
||||
description: "Value corresponding to Fan Medium mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_high:
|
||||
description: "Value corresponding to Fan High mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_auto:
|
||||
description: "Value corresponding to Fan Auto mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_top:
|
||||
description: "Value corresponding to Fan Top mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_middle:
|
||||
description: "Value corresponding to Fan Middle mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_focus:
|
||||
description: "Value corresponding to Fan Focus mode."
|
||||
required: false
|
||||
type: integer
|
||||
state_fan_diffuse:
|
||||
description: "Value corresponding to Fan Diffuse mode."
|
||||
required: false
|
||||
type: integer
|
||||
hvac_onoff_register:
|
||||
description: "Address of On/Off state.
|
||||
When zero is read from this register, the HVAC state is set to Off, otherwise the `hvac_mode_register`
|
||||
|