@ -58,13 +58,13 @@ There is currently support for the following device types within Home Assistant:
## Basic Configuration
To use your KNX bus in your installation, add the following lines to your `configuration.yaml` file:
To use your KNX devices from Home Assistant, add the following lines to your `configuration.yaml` file:
```yaml
knx:
```
In order to make use of the various platforms that KNX offers you will need to add the relevant configuration sections to your setup. This could either all be in the Home Assistant main `configuration.yaml` file, or in a separate YAML file that you include in the main file or even be split into multiple dedicated files as shown below:
In order to make use of the various platforms that KNX offers you will need to add the relevant configuration sections to your setup. This could either all be in the Home Assistant main `configuration.yaml` file, or in a separate YAML file that you include in the main file or even be split into multiple dedicated files. See [Splitting up the configuration](/docs/configuration/splitting_configuration/).
```yaml
knx:
@ -107,6 +107,33 @@ state_updater:
type: boolean
{% endconfiguration %}
### Group addresses
Group addresses are configured as strings or integers in the format "1/2/3" for 3-level GA-structure, "1/2" for 2-level GA-structure or "1" for free GA-structure.
The HA KNX integration uses configured `state_address` or `*_state_address` to update the state of a function. These addresses are read by GroupValueRead requests on startup and when there was no incoming telegram for one hour (default `sync_state`).
It is possible to configure passive/listening group addresses for all functions of every KNX platform (except `expose` and `notify`). This allows having multiple group addresses to update the state of its function (e.g., the brightness of a light). When group addresses are configured as a list of strings, the first item is the active sending or state-reading address and the rest is registered as passive addresses. This schema behaves like in ETS configuration where the first is the "sending" address and others are just for updating the communication object.
If your KNX device provides active state communication objects it is advised to use `*_state_address` instead of passive addresses as it reduces configuration complexity and avoids wrong states (e.g., when channels are logically locked).
```yaml
knx:
switch:
- name: "Switch without passive addresses"
address: "1/1/1" # this is the address that will be sent to
state_address: "8/8/8" # this is the address GroupValueRead requests are sent to
- name: "Switch with passive addresses"
address:
- "1/1/1" # this is the address that will be sent to
- "1/1/2" # this and following are passive addresses
- "1/1/3"
state_address:
- "8/8/8" # this is the address GroupValueRead requests are sent to
- "8/8/2" # this and following are passive addresses
- "8/8/3"
```
## Connection
Under normal conditions no connection configuration should be needed. The integration will auto-detect KNX/IP interfaces and connect to one. This requires multicast communication to work in your environment.
@ -261,7 +288,7 @@ The `knx.event_register` service can be used to register (or unregister) group a
address:
description: Group address that shall be added or removed.
required: true
type: string
type: [string, list]
remove:
description: If `True` the group address will be removed.
required: false
@ -357,7 +384,7 @@ knx:
state_address:
description: KNX group address of the binary sensor. *DPT 1*
required: true
type: string
type: [string, list]
name:
description: A name for this device used within Home Assistant.
required: false
@ -563,7 +590,7 @@ name:
temperature_address:
description: KNX group address for reading current room temperature from KNX bus. *DPT 9.001*
required: true
type: string
type: [string, list]
temperature_step:
description: Defines the step size in Kelvin for each step of setpoint_shift.
required: false
@ -572,19 +599,19 @@ temperature_step:
target_temperature_address:
description: KNX group address for setting target temperature. *DPT 9.001*
required: false
type: string
type: [string, list]
target_temperature_state_address:
description: KNX group address for reading current target temperature from KNX bus. *DPT 9.001*
required: true
type: string
type: [string, list]
setpoint_shift_address:
description: KNX address for setpoint_shift. *DPT 6.010 or DPT 9.002 based on setpoint_shift_mode*
required: false
type: string
type: [string, list]
setpoint_shift_state_address:
description: KNX address for reading setpoint_shift. *DPT 6.010 or DPT 9.002 based on setpoint_shift_mode*
required: false
type: string
type: [string, list]
setpoint_shift_mode:
description: Defines the internal device DPT used. Either 'DPT6010' or 'DPT9002'.
required: false
@ -603,51 +630,51 @@ setpoint_shift_max:
operation_mode_address:
description: KNX address for setting operation mode (Frost protection/night/comfort). *DPT 20.102*
required: false
type: string
type: [string, list]
operation_mode_state_address:
description: KNX address for reading operation mode. *DPT 20.102*
required: false
type: string
type: [string, list]
controller_status_address:
description: KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3).
required: false
type: string
type: [string, list]
controller_status_state_address:
description: KNX address for reading HVAC controller status.
required: false
type: string
type: [string, list]
controller_mode_address:
description: KNX address for setting HVAC controller modes. *DPT 20.105*
required: false
type: string
type: [string, list]
controller_mode_state_address:
description: KNX address for reading HVAC control mode. *DPT 20.105*
required: false
type: string
type: [string, list]
heat_cool_address:
description: KNX address for switching between heat/cool mode. *DPT 1.100*
required: false
type: string
type: [string, list]
heat_cool_state_address:
description: KNX address for reading heat/cool mode. *DPT 1.100*
required: false
type: string
type: [string, list]
operation_mode_frost_protection_address:
description: KNX address for switching on/off frost/heat protection mode. *DPT 1*
required: false
type: string
type: [string, list]
operation_mode_night_address:
description: KNX address for switching on/off night mode. *DPT 1*
required: false
type: string
type: [string, list]
operation_mode_comfort_address:
description: KNX address for switching on/off comfort mode. *DPT 1*
required: false
type: string
type: [string, list]
operation_mode_standby_address:
description: KNX address for switching on/off standby mode. *DPT 1*
required: false
type: string
type: [string, list]
operation_modes:
description: Overrides the supported operation modes. Provide the supported `preset_mode` values for your device.
required: false
@ -659,7 +686,7 @@ controller_modes:
on_off_address:
description: KNX address for switching the climate device on/off. *DPT 1*
required: false
type: string
type: [string, list]
on_off_invert:
description: Value for switching the climate device on/off is inverted.
required: false
@ -668,7 +695,7 @@ on_off_invert:
on_off_state_address:
description: KNX address for gathering the current state (on/off) of the climate device. *DPT 1*
required: false
type: string
type: [string, list]
min_temp:
description: Override the minimum temperature.
required: false
@ -713,31 +740,31 @@ name:
move_long_address:
description: KNX group address for moving the cover full up or down. *DPT 1*
required: false
type: string
type: [string, list]
move_short_address:
description: KNX group address for moving the cover short time up or down. Used by some covers also as the means to stop the cover, if no dedicated `stop_address` exists on the actuator. *DPT 1*
required: false
type: string
type: [string, list]
stop_address:
description: KNX group address for stopping the current movement from the cover. *DPT 1*
required: false
type: string
type: [string, list]
position_address:
description: KNX group address for moving the cover to the dedicated position. *DPT 5.001*
required: false
type: string
type: [string, list]
position_state_address:
description: Separate KNX group address for requesting the current position of the cover. *DPT 5.001*
required: false
type: string
type: [string, list]
angle_address:
description: KNX group address for moving the cover to the dedicated angle. *DPT 5.001*
required: false
type: string
type: [string, list]
angle_state_address:
description: Separate KNX group address for requesting the current angle of cover. *DPT 5.001*
required: false
type: string
type: [string, list]
travelling_time_down:
description: Time cover needs to travel down in seconds. Needed to calculate the intermediate positions of cover while traveling.
required: false
@ -790,19 +817,19 @@ name:
address:
description: KNX group address for setting the percentage or step of the fan. *DPT 5.001* or *DPT 5.010*
required: true
type: string
type: [string, list]
state_address:
description: KNX group address for retrieving the percentage or step of the fan. *DPT 5.001* or *DPT 5.010*
required: false
type: string
type: [string, list]
oscillation_address:
description: KNX group address for switching the fan oscillation on or off. *DPT 1*
required: false
type: string
type: [string, list]
oscillation_state_address:
description: KNX group address for retrieving the state of the fan oscillation. *DPT 1*
required: false
type: string
type: [string, list]
max_step:
description: The maximum amount of steps for a step-controlled fan. If set, the integration will convert percentages to steps automatically.
required: false
@ -832,11 +859,11 @@ knx:
address:
description: KNX group address for switching the light on and off. *DPT 1.001*
required: true
type: string
type: [string, list]
state_address:
description: KNX group address for retrieving the switch state of the light. *DPT 1.001*
required: false
type: string
type: [string, list]
name:
description: A name for this device used within Home Assistant.
required: false
@ -844,27 +871,27 @@ name:
brightness_address:
description: KNX group address for setting the brightness of the light in percent (absolute dimming). *DPT 5.001*
required: false
type: string
type: [string, list]
brightness_state_address:
description: KNX group address for retrieving the brightness of the light in percent. *DPT 5.001*
required: false
type: string
type: [string, list]
color_address:
description: KNX group address for setting the RGB color of the light. *DPT 232.600*
required: false
type: string
type: [string, list]
color_state_address:
description: KNX group address for retrieving the RGB color of the light. *DPT 232.600*
required: false
type: string
type: [string, list]
rgbw_address:
description: KNX group address for setting the RGBW color of the light. *DPT 251.600*
required: false
type: string
type: [string, list]
rgbw_state_address:
description: KNX group address for retrieving the RGBW color of the light. *DPT 251.600*
required: false
type: string
type: [string, list]
individual_colors:
description: Used when the actuator only supports individual group addresses for colors. When `address` is specified for all 3 (or 4) individual colors the root `address` key can be omitted.
required: false
@ -877,21 +904,19 @@ individual_colors:
keys:
address:
description: KNX group address to switch the red component. *DPT 1.001*
type: string
type: [string, list]
required: false
state_address:
description: KNX group address for the state of the red component. *DPT 1.001*
type: string
type: [string, list]
required: false
brightness_address:
description: KNX group address to set the brightness of the red component. *DPT 5.001*
type: string
type: [string, list]
required: true
brightness_state_address:
description: KNX group address for the current brightness of the red component. *DPT 5.001*
type: string
required: false
type: string
type: [string, list]
required: false
green:
description: Group addresses for the green component. Same keys available as for red component above.
@ -908,11 +933,11 @@ individual_colors:
color_temperature_address:
description: KNX group address for setting the color temperature of the light. *DPT 5.001 or 7.600 based on color_temperature_mode*
required: false
type: string
type: [string, list]
color_temperature_state_address:
description: KNX group address for retrieving the color temperature of the light. *DPT 5.001 or 7.600 based on color_temperature_mode*
required: false
type: string
type: [string, list]
color_temperature_mode:
description: Color temperature group address data type. `absolute` color temperature in Kelvin. *color_temperature_address -> DPT 7.600*. `relative` color temperature in percent cold white (0% warmest; 100% coldest). *color_temperature_address -> DPT 5.001*
required: false
@ -990,7 +1015,7 @@ knx:
address:
description: KNX group address of the notification. *DPT 16.000*
required: true
type: string
type: [string, list]
name:
description: A name for this device used within Home Assistant.
required: false
@ -1014,7 +1039,7 @@ knx:
address:
description: KNX group address for the scene. *DPT 17.001*
required: true
type: string
type: [string, list]
scene_number:
description: KNX scene number to be activated (range 1..64 ).
required: true
@ -1056,7 +1081,7 @@ knx:
state_address:
description: KNX group address of the sensor.
required: true
type: string
type: [string, list]
type:
description: A type from the value types table below must be defined. The DPT of the group address should match the expected KNX DPT to be parsed correctly.
required: true
@ -1262,7 +1287,7 @@ knx:
address:
description: KNX group address for switching the switch on/off. *DPT 1*
required: true
type: string
type: [string, list]
name:
description: A name for this device used within Home Assistant.
required: false
@ -1271,7 +1296,7 @@ name:
state_address:
description: Separate KNX group address for retrieving the switch state. *DPT 1*
required: false
type: string
type: [string, list]
invert:
description: Invert the telegrams payload before processing or sending.
required: false
@ -1318,55 +1343,55 @@ name:
address_temperature:
description: KNX group address for reading current outside temperature from KNX bus. *DPT 9.001*
required: true
type: string
type: [string, list]
address_brightness_south:
description: KNX group address for reading current brightness to south coordinate from KNX bus. *DPT 9.004*
required: false
type: string
type: [string, list]
address_brightness_west:
description: KNX group address for reading current brightness to west coordinate from KNX bus. *DPT 9.004*
required: false
type: string
type: [string, list]
address_brightness_east:
description: KNX group address for reading current brightness to east coordinate from KNX bus. *DPT 9.004*
required: false
type: string
type: [string, list]
address_brightness_north:
description: KNX group address for reading current brightness to north coordinate from KNX bus. *DPT 9.004*
required: false
type: string
type: [string, list]
address_wind_bearing:
description: KNX group address for reading current wind bearing from KNX bus. *DPT 5.003*
required: false
type: string
type: [string, list]
address_wind_speed:
description: KNX group address for reading current wind speed from KNX bus. *DPT 9.005*
required: false
type: string
type: [string, list]
address_rain_alarm:
description: KNX group address for reading if rain alarm is on/off.
required: false
type: string
type: [string, list]
address_frost_alarm:
description: KNX group address for reading if frost alarm is on/off.
required: false
type: string
type: [string, list]
address_wind_alarm:
description: KNX group address for reading if wind alarm is on/off.
required: false
type: string
type: [string, list]
address_day_night:
description: KNX group address for reading if it's day/night.
required: false
type: string
type: [string, list]
address_air_pressure:
description: KNX address reading current air pressure. *DPT 9.006*
required: false
type: string
type: [string, list]
address_humidity:
description: KNX address for reading current humidity. *DPT 9.007*
required: false
type: string
type: [string, list]
create_sensors:
description: If true, dedicated sensor entities are created for all configured properties.