--- layout: page title: "KNX Climate" description: "Instructions on how to integrate KNX thermostats with Home Assistant." date: 2016-06-24 12:00 sidebar: true comments: false sharing: true footer: true logo: knx.png ha_category: Climate ha_release: 0.25 ha_iot_class: "Local Polling" --- The `knx` climate platform is used as in interface with KNX thermostats. The `knx` component must be configured correctly, see [KNX Component](/components/knx). To use your KNX thermostats in your installation, add the following lines to your `configuration.yaml` file: ```yaml climate: - platform: knx name: HASS-Kitchen.Temperature temperature_address: '6/2/1' setpoint_address: '5/1/2' target_temperature_address: '5/1/1' operation_mode_address: '5/1/3' ``` Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode: ```yaml climate: - platform: knx name: HASS-Kitchen.Temperature temperature_address: '6/2/1' setpoint_address: '5/1/2' target_temperature_address: '5/1/1' operation_mode_frost_protection_address: '5/1/3' operation_mode_night_address: '5/1/4' operation_mode_comfort_address: '5/1/5' ``` * **name** (*Optional*): A name for this device used within Home Assistant. * **temperature_address**: KNX group address for reading current room temperature from KNX bus. * **target_temperature_address**: KNX group address for reading current target temperature from KNX bus. * **setpoint_address**: KNX group address for basis setpoint * **operation_mode_address** (*Optional*) KNX address for operation mode (Frost protection/night/comfort). * **operation_mode_state_address** (*Optional*) Explicit KNX address for reading operation mode * **controller_status_address** (*Optional*) KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3) * **controller_status_state_address** (*Optional*) Explicit KNX address for reading HVAC controller status * **operation_mode_frost_protection_address** (*Optional*) KNX address for switching on/off frost/heat protection mode. * **operation_mode_night_address** (*Optional*) KNX address for switching on/off night mode. * **operation_mode_comfort_address** (*Optional*) KNX address for switching on/off comfort mode. `operation_mode_frost_protection_address` / `operation_mode_night_address` / `operation_mode_comfort_address` are not necessary if `operation_mode_address` was specified.