--- layout: page title: "KNX Climate" description: "Instructions on how to integrate KNX thermostats with Home Assistant." date: 2016-06-24 12:00 sidebar: true comments: false sharing: true footer: true logo: knx.png ha_category: Climate ha_release: 0.25 ha_iot_class: "Local Polling" --- The `knx` climate platform is used as in interface with KNX thermostats. The `knx` component must be configured correctly, see [KNX Component](/components/knx). To use your KNX thermostats in your installation, add the following lines to your `configuration.yaml` file: ```yaml # Example configuration.yaml entry climate: - platform: knx name: HASS-Kitchen.Temperature temperature_address: '5/1/1' setpoint_shift_address: '5/1/2' setpoint_shift_state_address: '5/1/3' target_temperature_address: '5/1/4' operation_mode_address: '5/1/5' ``` Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode: ```yaml # Example configuration.yaml entry climate: - platform: knx name: HASS-Kitchen.Temperature temperature_address: '5/1/1' setpoint_shift_address: '5/1/2' setpoint_shift_state_address: '5/1/3' target_temperature_address: '5/1/4' operation_mode_frost_protection_address: '5/1/5' operation_mode_night_address: '5/1/6' operation_mode_comfort_address: '5/1/7' ``` Configuration variables: - **name** (*Optional*): A name for this device used within Home Assistant. - **temperature_address**: KNX group address for reading current room temperature from KNX bus. - **target_temperature_address**: KNX group address for reading current target temperature from KNX bus. The `knx` component sets the desired target temperature by modifying the setpoint_shift. The module provides the following configuration options: * **setpoint_shift_address**: (*Optional*) KNX address for setpoint_shift * **setpoint_shift_state_address**: (*Optional*) Explicit KNX address for reading setpoint_shift. * **setpoint_shift_step**: (*Optional*) Defines for step size in Kelvin for each step of setpoint_shift. Default is 0.5 K. * **setpoint_shift_min**: (*Optional*) Minimum value of setpoint shift. Default is "-6". * **setpoint_shift_max**: (*Optional*) Maximum value of setpoint shift. Default is "6". The operation modes may be controlled with the following directives: - **operation_mode_address** (*Optional*): KNX address for operation mode (Frost protection/night/comfort). - **operation_mode_state_address** (*Optional*): Explicit KNX address for reading operation mode - **controller_status_address** (*Optional*): KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3) - **controller_status_state_address** (*Optional*): Explicit KNX address for reading HVAC controller status - **operation_mode_frost_protection_address** (*Optional*): KNX address for switching on/off frost/heat protection mode. - **operation_mode_night_address** (*Optional*): KNX address for switching on/off night mode. - **operation_mode_comfort_address** (*Optional*): KNX address for switching on/off comfort mode. `operation_mode_frost_protection_address` / `operation_mode_night_address` / `operation_mode_comfort_address` are not necessary if `operation_mode_address` was specified.