--- layout: page title: "KNX Climate" description: "Instructions on how to integrate KNX thermostats with Home Assistant." date: 2016-06-24 12:00 sidebar: true comments: false sharing: true footer: true logo: knx.png ha_category: Climate ha_release: 0.25 ha_iot_class: "Local Polling" --- The `knx` climate platform is used as in interface with KNX thermostats. The `knx` component must be configured correctly, see [KNX Component](/components/knx). To use your KNX thermostats in your installation, add the following lines to your `configuration.yaml` file: ```yaml # Example configuration.yaml entry climate: - platform: knx name: HASS-Kitchen.Temperature temperature_address: '5/1/1' setpoint_shift_address: '5/1/2' setpoint_shift_state_address: '5/1/3' target_temperature_address: '5/1/4' operation_mode_address: '5/1/5' ``` Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode: ```yaml # Example configuration.yaml entry climate: - platform: knx name: HASS-Kitchen.Temperature temperature_address: '5/1/1' setpoint_shift_address: '5/1/2' setpoint_shift_state_address: '5/1/3' target_temperature_address: '5/1/4' operation_mode_frost_protection_address: '5/1/5' operation_mode_night_address: '5/1/6' operation_mode_comfort_address: '5/1/7' ``` {% configuration %} name: description: A name for this device used within Home Assistant. required: false default: KNX Climate type: string temperature_address: description: KNX group address for reading current room temperature from KNX bus. required: true type: string target_temperature_address: description: KNX group address for reading current target temperature from KNX bus. required: true type: string setpoint_shift_address: description: KNX address for setpoint_shift. required: false type: string setpoint_shift_state_address: description: Explicit KNX address for reading setpoint_shift. required: false type: string setpoint_shift_step: description: Defines for step size in Kelvin for each step of setpoint_shift. required: false default: 0.5 type: float setpoint_shift_min: description: Minimum value of setpoint shift. required: false default: -6 type: integer setpoint_shift_max: description: Maximum value of setpoint shift. required: false default: 6 type: integer operation_mode_address: description: KNX address for operation mode (Frost protection/night/comfort). required: false type: string operation_mode_state_address: description: Explicit KNX address for reading operation mode. required: false type: string controller_status_address: description: KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3). required: false type: string controller_status_state_address: description: Explicit KNX address for reading HVAC controller status. required: false type: string operation_mode_frost_protection_address: description: KNX address for switching on/off frost/heat protection mode. required: false type: string operation_mode_night_address: description: KNX address for switching on/off night mode. required: false type: string operation_mode_comfort_address: description: KNX address for switching on/off comfort mode. required: false type: string {% endconfiguration %} `operation_mode_frost_protection_address` / `operation_mode_night_address` / `operation_mode_comfort_address` are not necessary if `operation_mode_address` is specified.