title: "KNX Climate"
|
|
description: "Instructions on how to integrate KNX thermostats with Home Assistant."
|
|
ha_category:
|
|
- Climate
|
|
ha_release: 0.25
|
|
ha_iot_class: Local Push
|
|
ha_domain: knx
|
|
---
|
|
|
|
<div class='note'>
|
|
|
|
The `knx` integration must be configured correctly to use this integration, see [KNX Integration](/integrations/knx).
|
|
|
|
</div>
|
|
|
|
The `knx` climate platform is used as an interface to KNX thermostats and room controllers.
|
|
|
|
To use your KNX thermostats in your installation, add the following lines to your `configuration.yaml` file:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
climate:
|
|
- platform: knx
|
|
name: HASS-Kitchen.Temperature
|
|
temperature_address: '5/1/1'
|
|
setpoint_shift_address: '5/1/2'
|
|
setpoint_shift_state_address: '5/1/3'
|
|
target_temperature_state_address: '5/1/4'
|
|
operation_mode_address: '5/1/5'
|
|
operation_mode_state_address: '5/1/6'
|
|
```
|
|
|
|
Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
climate:
|
|
- platform: knx
|
|
name: HASS-Kitchen.Temperature
|
|
temperature_address: '5/1/1'
|
|
setpoint_shift_address: '5/1/2'
|
|
setpoint_shift_state_address: '5/1/3'
|
|
target_temperature_state_address: '5/1/4'
|
|
operation_mode_frost_protection_address: '5/1/5'
|
|
operation_mode_night_address: '5/1/6'
|
|
operation_mode_comfort_address: '5/1/7'
|
|
operation_mode_state_address: '5/1/8'
|
|
```
|
|
|
|
If your device doesn't support setpoint_shift calculations (i.e., if you don't provide a `setpoint_shift_address` value) please set the `min_temp` and `max_temp`
|
|
attributes of the climate device to avoid issues with exceeding valid temperature values in the frontend. Please do also make sure to add the `target_temperature_address`
|
|
to the configuration in this case.:
|
|
|
|
```yaml
|
|
# Example configuration.yaml entry
|
|
climate:
|
|
- platform: knx
|
|
name: HASS-Kitchen.Temperature
|
|
temperature_address: '5/1/2'
|
|
target_temperature_address: '5/1/4'
|
|
target_temperature_state_address: '5/1/1'
|
|
operation_mode_frost_protection_address: '5/1/5'
|
|
operation_mode_night_address: '5/1/6'
|
|
operation_mode_comfort_address: '5/1/7'
|
|
operation_mode_state_address: '5/1/8'
|
|
min_temp: 7.0
|
|
max_temp: 32.0
|
|
```
|
|
|
|
`operation_mode_frost_protection_address` / `operation_mode_night_address` / `operation_mode_comfort_address` are not necessary if `operation_mode_address` is specified.
|
|
If the actor doesn't support explicit state communication objects the *_state_address can be configured with the same group address as the writeable *_address. The Read-Flag for the *_state_address communication object has to be set in ETS to support initial reading e.g., when starting Home Assistant.
|
|
|
|
The following values are valid for the `hvac_mode` attribute:
|
|
|
|
- Off (maps internally to HVAC_MODE_OFF within Home Assistant)
|
|
- Auto (maps internally to HVAC_MODE_AUTO within Home Assistant)
|
|
- Heat (maps internally to HVAC_MDOE_HEAT within Home Assistant)
|
|
- Cool (maps internally to HVAC_MDOE_COOL within Home Assistant)
|
|
- Fan only (maps internally to HVAC_MODE_FAN_ONLY within Home Assistant)
|
|
- Dry (maps internally to HVAC_MODE_DRY within Home Assistant)
|
|
|
|
The following presets are valid for the `preset_mode` attribute:
|
|
|
|
- Comfort (maps internally to PRESET_COMFORT within Home Assistant)
|
|
- Standby (maps internally to PRESET_AWAY within Home Assistant)
|
|
- Night (maps internally to PRESET_SLEEP within Home Assistant)
|
|
- Frost Protection (maps internally to PRESET_ECO within Home Assistant)
|
|
|
|
{% configuration %}
|
|
name:
|
|
description: A name for this device used within Home Assistant.
|
|
required: false
|
|
default: KNX Climate
|
|
type: string
|
|
temperature_address:
|
|
description: KNX group address for reading current room temperature from KNX bus. *DPT 9.001*
|
|
required: true
|
|
type: string
|
|
target_temperature_address:
|
|
description: KNX group address for setting target temperature. *DPT 9.001*
|
|
required: false
|
|
type: string
|
|
target_temperature_state_address:
|
|
description: KNX group address for reading current target temperature from KNX bus. *DPT 9.001*
|
|
required: true
|
|
type: string
|
|
setpoint_shift_address:
|
|
description: KNX address for setpoint_shift. *DPT 6.010*
|
|
required: false
|
|
type: string
|
|
setpoint_shift_state_address:
|
|
description: KNX address for reading setpoint_shift. *DPT 6.010*
|
|
required: false
|
|
type: string
|
|
setpoint_shift_step:
|
|
description: Defines the step size in Kelvin for each step of setpoint_shift.
|
|
required: false
|
|
default: 0.5
|
|
type: float
|
|
setpoint_shift_min:
|
|
description: Minimum value of setpoint shift.
|
|
required: false
|
|
default: -6
|
|
type: float
|
|
setpoint_shift_max:
|
|
description: Maximum value of setpoint shift.
|
|
required: false
|
|
default: 6
|
|
type: float
|
|
operation_mode_address:
|
|
description: KNX address for setting operation mode (Frost protection/night/comfort). *DPT 20.102*
|
|
required: false
|
|
type: string
|
|
operation_mode_state_address:
|
|
description: KNX address for reading operation mode. *DPT 20.102*
|
|
required: false
|
|
type: string
|
|
controller_status_address:
|
|
description: KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3).
|
|
required: false
|
|
type: string
|
|
controller_status_state_address:
|
|
description: KNX address for reading HVAC controller status.
|
|
required: false
|
|
type: string
|
|
controller_mode_address:
|
|
description: KNX address for setting HVAC controller modes. *DPT 20.105*
|
|
required: false
|
|
type: string
|
|
controller_mode_state_address:
|
|
description: KNX address for reading HVAC Control Mode. *DPT 20.105*
|
|
required: false
|
|
type: string
|
|
operation_mode_frost_protection_address:
|
|
description: KNX address for switching on/off frost/heat protection mode.
|
|
required: false
|
|
type: string
|
|
operation_mode_night_address:
|
|
description: KNX address for switching on/off night mode.
|
|
required: false
|
|
type: string
|
|
operation_mode_comfort_address:
|
|
description: KNX address for switching on/off comfort mode.
|
|
required: false
|
|
type: string
|
|
operation_modes:
|
|
description: Overrides the supported operation modes. Provide the supported `hvac_mode` and `preset_mode` values for your device.
|
|
required: false
|
|
type: list
|
|
on_off_address:
|
|
description: KNX address for switching the climate device on/off.
|
|
required: false
|
|
type: string
|
|
on_off_invert:
|
|
description: Value for switching the climate device on/off is inverted.
|
|
required: false
|
|
default: false
|
|
type: boolean
|
|
on_off_state_address:
|
|
description: KNX address for gathering the current state (on/off) of the climate device.
|
|
required: false
|
|
type: string
|
|
min_temp:
|
|
description: Override the minimum temperature.
|
|
required: false
|
|
type: float
|
|
max_temp:
|
|
description: Override the maximum temperature.
|
|
required: false
|
|
type: float
|
|