80 KiB
title | description | ha_category | ha_release | ha_iot_class | ha_codeowners | ha_domain | ha_quality_scale | ha_platforms | ha_config_flow | ha_integration_type | |||||||||||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
KNX | Instructions on how to integrate KNX components with Home Assistant. |
|
0.24 | Local Push |
|
knx | platinum |
|
true | hub |
The KNX integration for Home Assistant allows you to connect to KNX/IP devices.
The integration requires a local KNX/IP interface or router. Through this, it will establish a connection between Home Assistant and your KNX bus.
There is currently support for the following device types within Home Assistant:
{% include integrations/config_flow.md %}
Basic Configuration
In order to make use of the various platforms that KNX offers you will need to add the relevant configuration sections to your setup. This could either all be in the Home Assistant main configuration.yaml
file, or in a separate YAML file that you include in the main file or even be split into multiple dedicated files. See Splitting up the configuration.
knx:
# configure platforms directly in configuration.yaml
binary_sensor:
- name: "My first binary sensor"
state_address: "1/2/3"
# etc...
# or outsource platform configuration to separate files
sensor: !include knx_sensor.yaml
Please see the dedicated platform sections below about how to configure them correctly.
Group addresses
Group addresses are configured as strings or integers in the format "1/2/3" for 3-level GA-structure, "1/2" for 2-level GA-structure or "1" for free GA-structure.
The HA KNX integration uses configured state_address
or *_state_address
to update the state of a function. These addresses are read by GroupValueRead requests on startup and when there was no incoming telegram for one hour (default sync_state
).
It is possible to configure passive/listening group addresses for all functions of every KNX platform (except expose
and notify
). This allows having multiple group addresses to update the state of its function (e.g., the brightness of a light). When group addresses are configured as a list of strings, the first item is the active sending or state-reading address and the rest is registered as passive addresses. This schema behaves like in ETS configuration where the first is the "sending" address and others are just for updating the group object.
If your KNX device provides active state group objects it is advised to use *_state_address
instead of passive addresses as it reduces configuration complexity and avoids wrong states (e.g., when channels are logically locked).
knx:
switch:
- name: "Switch without passive addresses"
address: "1/1/1" # this is the address that will be sent to
state_address: "8/8/8" # this is the address GroupValueRead requests are sent to
- name: "Switch with passive addresses"
address:
- "1/1/1" # this is the address that will be sent to
- "1/1/2" # this and following are passive addresses
- "1/1/3"
state_address:
- "8/8/8" # this is the address GroupValueRead requests are sent to
- "8/8/2" # this and following are passive addresses
- "8/8/3"
Connection
Connection parameters are set up when adding the integration and can be changed from the Integrations
panel.
Use route back
if your tunneling server is located on a different network.
KNX Secure
The KNX integration supports IP Secure and Data Secure .
You can configure the IP Secure credentials either manually or by providing a .knxkeys
file, which you can obtain by exporting the keyring in ETS as seen in the screenshot below.
Data Secure credentials are always sourced from a .knxkeys
file. You can import or update the Keyring file from the integrations settings.
For Data Secure, please make sure that all secured group addresses you want to use in Home Assistant are assigned to a tunnel of your interface or a dummy device in ETS and all participating devices are updated accordingly.
If you decide to configure IP Secure manually you will need the user ID, the user password and the device authentication password.
The user id 0 is reserved and the user id 1 is used for management tasks, thus you will need to specify a user id that is 2 or higher according to the tunneling channel you would like to use.
The following screenshot will show how you can get the device authentication password in ETS.
The user password can be obtained almost the same way as seen in the below screenshot.
Events
knx:
event:
- address:
- "0/1/*"
- address:
- "1/2/*"
- "1/3/2-4"
type: "2byte_unsigned"
- address:
- "3/4/5"
type: "2byte_float"
{% configuration %}
address:
description: Defines a list of patterns for matching KNX group addresses. Telegrams with destination addresses matching one of the patterns are sent to the Home Assistant event bus as knx_event
.
required: true
type: [list, string]
type:
description: Telegram payloads in knx_event
events will be decoded using the configured type (DPT) for the addresses in the same block. The decoded value will be written to the event data value
key. If not configured the value
key will be None
- the data
key will still hold the raw payload (use this for DPT 1, 2, 3). All sensor types are valid types - see KNX Sensor (e.g., "2byte_float" or "1byte_signed").
type: [string, integer]
required: false
{% endconfiguration %}
Every telegram that matches an address pattern with its destination field will be announced on the event bus as a knx_event
event containing data attributes
data
contains the raw payload data (e.g., 1 or "[12, 55]").destination
the KNX group address the telegram is sent to as string (e.g., "1/2/3").direction
the direction of the telegram as string ("Incoming" / "Outgoing").source
the KNX individual address of the sender as string (e.g., "1.2.3").telegramtype
the APCI service of the telegram. "GroupValueWrite", "GroupValueRead" or "GroupValueResponse" generate a knx_event.value
contains the decoded payload value iftype
is configured for the address. Will beNone
for "GroupValueRead" telegrams.
Services
In order to directly interact with the KNX bus, you can use the following services:
Send
Domain: knx
Service: send
Service Data: {"address": "1/0/15", "payload": 0, "type": "temperature"}
{% configuration %}
address:
description: KNX group address.
type: string
payload:
description: Payload to send to the bus. When type
is not set, raw bytes are sent. Integers are then treated as DPT 1/2/3 payloads. For DPTs > 6 bits send a list. Each value represents 1 octet (0-255). Pad with 0 to DPT byte length.
type: [integer, list]
type:
description: If set, the payload will not be sent as raw bytes, but encoded as given DPT. KNX sensor types are valid values - see table in KNX Sensor.
type: [string, integer, float]
response:
description: If set to true
, the telegram will be sent as a GroupValueResponse
instead of a GroupValueWrite
.
type: boolean
default: false
{% endconfiguration %}
Read
You can use the homeassistant.update_entity
service call to issue GroupValueRead requests for all *state_address
of an entity.
To manually send GroupValueRead requests use the knx.read
service. The response can be used from knx_event
and will be processed in KNX entities.
Domain: knx
Service: read
Service Data: {"address": "1/0/15"}
{% configuration %} address: description: Group address(es) to send read request to. Lists will read multiple group addresses. type: [string, list] {% endconfiguration %}
# Example automation to update a cover position after 10 seconds of movement initiation
automation:
- trigger:
- platform: event
event_type: knx_event
event_data:
# Cover move trigger
destination: "0/4/20"
action:
- delay: 0:0:10
- service: knx.read
data:
# Cover position address
address: "0/4/21"
- trigger:
- platform: homeassistant
event: start
action:
# Register the group address to trigger a knx_event
- service: knx.event_register
data:
# Cover move trigger
address: "0/4/20"
- service: knx.read
data:
# Cover position address
address: "0/4/21"
Register Event
The knx.event_register
service can be used to register (or unregister) group addresses to fire knx_event
Events. Events for group addresses configured in the event
key in configuration.yaml
cannot be unregistered. See knx_event
{% configuration %}
address:
description: Group address that shall be added or removed.
required: true
type: [string, list]
remove:
description: If True
the group address will be removed.
required: false
type: boolean
default: false
type:
description: If set, the payload will be decoded as given DPT in the event data value
key. KNX sensor types are valid values KNX Sensor (e.g., "2byte_float" or "1byte_signed").
type: [string, integer]
required: false
{% endconfiguration %}
Register Exposure
The knx.exposure_register
service can be used to register (or unregister) exposures to the KNX bus. Exposures defined in configuration.yaml
can not be unregistered. Per address only one exposure can be registered. See expose
{% configuration %}
remove:
description: In addition to the configuration variables of expose remove
set to True
can be used to remove exposures. Only address
is required for removal.
required: false
type: boolean
default: false
{% endconfiguration %}
Exposing entity states, entity attributes or time to KNX bus
KNX integration is able to expose entity states or attributes to KNX bus. The integration will broadcast any change of the exposed value to the KNX bus and answer read requests to the specified group address. It is also possible to expose the current time and date. These are sent to the bus every hour.
Expose is only triggered on state changes. If you need periodical telegrams, use an automation with the knx.send
service to send the value to the bus.
# Example configuration.yaml entry
knx:
expose:
- type: temperature
entity_id: sensor.owm_temperature
address: "0/0/2"
cooldown: 600
- type: string
address: "0/6/4"
entity_id: sensor.owm_weather
- type: binary
entity_id: binary_sensor.kitchen_window
address: "0/6/5"
- type: binary
entity_id: light.office
address: "0/3/0"
default: false
- type: percentU8
entity_id: light.office
attribute: brightness
default: 0
address: "0/3/1"
- type: time
address: "0/0/1"
- type: datetime
address: "0/0/23"
{% configuration %}
address:
description: Group address state or attribute updates will be sent to. GroupValueRead requests will be answered.
type: string
required: true
type:
description: Type of the exposed value. Either binary
, time
, date
, datetime
or any supported type of KNX Sensor (e.g., "temperature" or "humidity").
type: [string, integer]
required: true
entity_id:
description: Entity ID to be exposed. Not needed for types time
, date
and datetime
.
type: string
required: false
attribute:
description: Attribute of the entity that shall be sent to the KNX bus. If not set (or None
) the state will be sent.
For example for a light the state is either "on" or "off". With attribute
you can expose its "brightness".
type: string
required: false
default:
description: Default value to send to the bus if the state or attribute value is None
.
For example a light with state "off" has no brightness attribute so a default value of 0
could be used.
If not set (or None
) no value would be sent to the bus and a GroupReadRequest to the address would return the last known value.
type: [boolean, string, integer, float]
default: None
required: false
cooldown:
description: Minimum time in seconds between two sent telegrams. This can be used to avoid flooding the KNX bus when exposing frequently changing states. If the state changes multiple times within the cooldown period the most recent value will be sent.
type: float
default: 0
required: false
respond_to_read:
description: Respond to GroupValueRead telegrams received to the configured address
.
required: false
type: boolean
default: true
{% endconfiguration %}
Binary Sensor
The KNX binary sensor platform allows you to monitor KNX binary sensors.
Binary sensors are read-only. To write to the KNX bus configure an exposure KNX Integration Expose.
knx:
binary_sensor:
- name: "Sensor 1"
state_address: "6/0/2"
{% configuration %}
state_address:
description: KNX group address of the binary sensor. DPT 1
required: true
type: [string, list]
name:
description: A name for this device used within Home Assistant.
required: false
type: string
sync_state:
description: Actively read the value from the bus. If false
no GroupValueRead telegrams will be sent to the bus. sync_state
can be set to init
to just initialize state on startup, expire <minutes>
to read the state from the KNX bus when no telegram was received for <minutes> or every <minutes>
to update it regularly every <minutes>. Maximum value for <minutes> is 1440. If just a number is configured "expire"-behaviour is used. Defaults to true
which is interpreted as "expire 60".
required: false
type: [boolean, string, integer]
default: true
device_class:
description: Sets the class of the device, changing the device state and icon that is displayed on the frontend.
required: false
type: string
reset_after:
description: Reset back to "off" state after specified seconds.
required: false
type: float
invert:
description: Invert the telegrams payload before processing. This is applied before context_timeout
or reset_after
is evaluated.
required: false
type: boolean
default: false
ignore_internal_state:
description: Specifies if telegrams should ignore the internal state and always trigger a Home Assistant state update.
required: false
type: boolean
default: false
context_timeout:
description: The time in seconds between multiple identical telegram payloads would count towards the internal counter that is used for automations. Ex. You have automations in place that trigger your lights on button press and another set of lights if you click that button twice. This setting defines the time that a second button press would count toward, so if you set this 3.0 you can take up to 3 seconds in order to trigger the second button press. If set ignore_internal_state
will be set to true
internally. Maximum value is 10.0.
required: false
type: float
default: None
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Support for automations
You can use a built in event in order to trigger an automation (e.g. to switch on a light when a switch was pressed).
Let's pretend you have a binary sensor with the name Livingroom.Switch
and you want to switch one light on when the button was pressed once and two other lights when the button was pressed twice. context_timeout
has to be configured in order for this to work.
# Example automation.yaml entry
automation:
- trigger:
platform: numeric_state
entity_id: binary_sensor.livingroom_switch
attribute: counter
above: 0
below: 2
condition:
- condition: state
entity_id: binary_sensor.cover_abstell
state: "on"
action:
- entity_id: light.hue_color_lamp_1
service: light.turn_on
- trigger:
platform: numeric_state
entity_id: binary_sensor.livingroom_switch
attribute: counter
above: 1
below: 3
condition:
- condition: state
entity_id: binary_sensor.cover_abstell
state: "on"
action:
- entity_id: light.hue_bloom_1
service: homeassistant.turn_on
- entity_id: light.hue_bloom_2
service: homeassistant.turn_on
{% configuration %} name: description: A name for this device used within Home Assistant. required: false type: string counter: description: Set to 2 if you only want the action to be executed if the button was pressed twice. Set to 3 for three times button pressed. required: false type: integer default: 1 hook: description: Indicates if the automation should be executed on what state of the binary sensor. Values are "on" or "off". required: false type: string default: "on" action: description: Specify a list of actions analog to the automation rules. required: false type: list {% endconfiguration %}
Button
The KNX button platform allows to send concurrent predefined values via the frontend or a platform service. When a user presses the button, the assigned generic raw payload is sent to the KNX bus.
Telegrams received on the KNX bus for the group address of a button are not reflected in a new button state. Use knx_event
if you want to automate on a specific payload received on a group address.
# Example configuration.yaml entry
knx:
button:
- name: "DPT 1 - True button"
address: "0/0/1"
- name: "100% button"
address: "0/0/2"
payload: 0xFF
payload_length: 1
- name: "Temperature button"
address: "0/0/3"
value: 21.5
type: temperature
When type
is used value
is required, payload
is invalid.
When payload_length
is used value
is invalid.
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
type: string
address:
description: Group address to send to.
required: true
type: [string, list]
payload:
description: The raw payload that shall be sent.
required: false
type: integer
default: 1
payload_length:
description: The length of the payload data in the telegram. Use 0
for DPT 1, 2 or 3.
required: false
type: integer
default: 0
value:
description: The value that shall be sent encoded by type
.
required: false
type: [integer, float, string]
type:
description: A type from the value types table to encode the configured value
.
required: false
type: [string, integer]
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Climate
The KNX climate platform is used as an interface to KNX thermostats and room controllers.
To use your KNX thermostats in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
climate:
- name: "Kitchen"
temperature_address: "5/1/1"
setpoint_shift_address: "5/1/2"
setpoint_shift_state_address: "5/1/3"
target_temperature_state_address: "5/1/4"
operation_mode_address: "5/1/5"
operation_mode_state_address: "5/1/6"
Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode:
# Example configuration.yaml entry
knx:
climate:
- name: "Kitchen"
temperature_address: "5/1/1"
setpoint_shift_address: "5/1/2"
setpoint_shift_state_address: "5/1/3"
target_temperature_state_address: "5/1/4"
operation_mode_frost_protection_address: "5/1/5"
operation_mode_night_address: "5/1/6"
operation_mode_comfort_address: "5/1/7"
operation_mode_state_address: "5/1/8"
If your device doesn't support setpoint_shift calculations (i.e., if you don't provide a setpoint_shift_address
value) please set the min_temp
and max_temp
attributes of the climate device to avoid issues with exceeding valid temperature values in the frontend. Please do also make sure to add the target_temperature_address
to the configuration in this case.:
# Example configuration.yaml entry
knx:
climate:
- name: "Kitchen"
temperature_address: "5/1/2"
target_temperature_address: "5/1/4"
target_temperature_state_address: "5/1/1"
operation_mode_frost_protection_address: "5/1/5"
operation_mode_night_address: "5/1/6"
operation_mode_comfort_address: "5/1/7"
operation_mode_state_address: "5/1/8"
operation_mode_standby_address: "5/1/9"
min_temp: 7.0
max_temp: 32.0
setpoint_shift_mode
allows the two following DPTs to be used:
- DPT6010 (for 1 byte signed integer with scale factor)
- DPT9002 (for 2 byte float)
Example:
# Example configuration.yaml entry
knx:
climate:
- name: "Kitchen"
temperature_address: "5/1/1"
setpoint_shift_address: "5/1/2"
setpoint_shift_state_address: "5/1/3"
setpoint_shift_mode: "DPT9002"
target_temperature_state_address: "5/1/4"
operation_mode_address: "5/1/5"
operation_mode_state_address: "5/1/6"
operation_mode_frost_protection_address
/ operation_mode_night_address
/ operation_mode_comfort_address
/ operation_mode_standby_address
are not necessary if operation_mode_address
is specified.
If the actor doesn't support explicit state group objects the *_state_address
can be configured with the same group address as the writeable *_address
. The read flag for the *_state_address
group object has to be set in ETS to support initial reading e.g., when starting Home Assistant.
The following values are valid for the heat_cool_address
and the heat_cool_state_address
:
0
(cooling)1
(heating)
The following values are valid for the Home Assistant Climate hvac_mode
attribute. Supported values for your KNX thermostats can be specified via controller_modes
configuration variable:
Off
(maps internally toHVAC_MODE_OFF
within Home Assistant)Auto
(maps internally toHVAC_MODE_AUTO
within Home Assistant)Heat
(maps internally toHVAC_MODE_HEAT
within Home Assistant)Cool
(maps internally toHVAC_MODE_COOL
within Home Assistant)Fan only
(maps internally toHVAC_MODE_FAN_ONLY
within Home Assistant)Dry
(maps internally toHVAC_MODE_DRY
within Home Assistant)
The following presets are valid for the Home Assistant Climate preset_mode
attribute. Supported values for your KNX thermostats can be specified via operation_modes
configuration variable:
Auto
(maps tonone
of the Home Assistant Climatepreset_mode
attribute)Comfort
(maps tocomfort
of the Home Assistant Climatepreset_mode
attribute)Standby
(maps toaway
of the Home Assistant Climatepreset_mode
attribute)Night
(maps tosleep
of the Home Assistant Climatepreset_mode
attribute)Frost Protection
(maps toeco
of the Home Assistant Climatepreset_mode
attribute)
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
default: KNX Climate
type: string
temperature_address:
description: KNX group address for reading current room temperature from KNX bus. DPT 9.001
required: true
type: [string, list]
temperature_step:
description: Defines the step size in Kelvin for each step of setpoint_shift (scale factor). For non setpoint-shift configurations this is used to set the step of temperature sliders in UI.
required: false
type: float
default: 0.1
target_temperature_address:
description: KNX group address for setting target temperature. DPT 9.001
required: false
type: [string, list]
target_temperature_state_address:
description: KNX group address for reading current target temperature from KNX bus. DPT 9.001
required: true
type: [string, list]
setpoint_shift_address:
description: KNX address for setpoint_shift. DPT 6.010 or DPT 9.002 based on setpoint_shift_mode
required: false
type: [string, list]
setpoint_shift_state_address:
description: KNX address for reading setpoint_shift. DPT 6.010 or DPT 9.002 based on setpoint_shift_mode
required: false
type: [string, list]
setpoint_shift_mode:
description: Defines the internal device DPT used. Either 'DPT6010', 'DPT9002' or None. When None
or omitted the DPT is auto-assigned from the first incoming telegram.
required: false
type: string
default: None
setpoint_shift_min:
description: Minimum value of setpoint shift.
required: false
default: -6
type: float
setpoint_shift_max:
description: Maximum value of setpoint shift.
required: false
default: 6
type: float
active_state_address:
description: KNX address for reading current activity. 0
is idle, 1
is active. DPT 1
required: false
type: [string, list]
command_value_state_address:
description: KNX address for reading current command value in percent. 0
sets the climate entity to idle if active_state_address
is not set. DPT 5.001
required: false
type: [string, list]
operation_mode_address:
description: KNX address for setting operation mode (Frost protection/night/comfort). DPT 20.102
required: false
type: [string, list]
operation_mode_state_address:
description: KNX address for reading operation mode. DPT 20.102
required: false
type: [string, list]
controller_status_address:
description: KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3).
required: false
type: [string, list]
controller_status_state_address:
description: KNX address for reading HVAC controller status.
required: false
type: [string, list]
controller_mode_address:
description: KNX address for setting HVAC controller modes. DPT 20.105
required: false
type: [string, list]
controller_mode_state_address:
description: KNX address for reading HVAC control mode. DPT 20.105
required: false
type: [string, list]
heat_cool_address:
description: KNX address for switching between heat/cool mode. DPT 1.100
required: false
type: [string, list]
heat_cool_state_address:
description: KNX address for reading heat/cool mode. DPT 1.100
required: false
type: [string, list]
operation_mode_frost_protection_address:
description: KNX address for switching on/off frost/heat protection mode. DPT 1
required: false
type: [string, list]
operation_mode_night_address:
description: KNX address for switching on/off night mode. DPT 1
required: false
type: [string, list]
operation_mode_comfort_address:
description: KNX address for switching on/off comfort mode. DPT 1
required: false
type: [string, list]
operation_mode_standby_address:
description: KNX address for switching on/off standby mode. DPT 1
required: false
type: [string, list]
operation_modes:
description: Overrides the supported operation modes. Provide the supported preset_mode
values for your device.
required: false
type: list
controller_modes:
description: Overrides the supported controller modes. Provide the supported hvac_mode
values for your device.
required: false
type: list
default_controller_mode:
description: Overrides the default controller mode. Any Home Assistant hvac_mode
can be configured. This can, for example, be set to "cool" for cooling-only devices.
required: false
default: "heat"
type: string
on_off_address:
description: KNX address for switching the climate device on/off. DPT 1
required: false
type: [string, list]
on_off_invert:
description: Value for switching the climate device on/off is inverted.
required: false
default: false
type: boolean
on_off_state_address:
description: KNX address for gathering the current state (on/off) of the climate device. DPT 1
required: false
type: [string, list]
min_temp:
description: Override the minimum temperature.
required: false
type: float
max_temp:
description: Override the maximum temperature.
required: false
type: float
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Cover
The KNX cover platform is used as an interface to KNX covers.
Unlike most KNX devices, Home Assistant defines 0% as closed and 100% as fully open in regards to covers. The corresponding value inversion is done internally by the KNX integration.
To use your KNX covers in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
cover:
- name: "Kitchen shutter"
move_long_address: "3/0/0"
move_short_address: "3/0/1"
stop_address: "3/0/4"
position_address: "3/0/3"
position_state_address: "3/0/2"
travelling_time_down: 51
travelling_time_up: 61
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
default: KNX Cover
type: string
move_long_address:
description: KNX group address for moving the cover full up or down. DPT 1
required: false
type: [string, list]
move_short_address:
description: KNX group address for moving the cover stepwise up or down. Used by some covers also as the means to stop the cover, if no dedicated stop_address
exists on the actuator. DPT 1
required: false
type: [string, list]
stop_address:
description: KNX group address for stopping the current movement of the cover. DPT 1
required: false
type: [string, list]
position_address:
description: KNX group address for moving the cover to the dedicated position. DPT 5.001
required: false
type: [string, list]
position_state_address:
description: Separate KNX group address for requesting the current position of the cover. DPT 5.001
required: false
type: [string, list]
angle_address:
description: KNX group address for tilting the cover to the dedicated angle. DPT 5.001
required: false
type: [string, list]
angle_state_address:
description: Separate KNX group address for requesting the current tilt angle of the cover. DPT 5.001
required: false
type: [string, list]
travelling_time_down:
description: Time cover needs to travel down in seconds. Needed to calculate the intermediate positions of cover while traveling.
required: false
default: 25
type: integer
travelling_time_up:
description: Time cover needs to travel up in seconds. Needed to calculate the intermediate positions of cover while traveling.
required: false
default: 25
type: integer
invert_updown:
description: Set this to true
to invert the binary up/down commands from/to your KNX actuator. Default is 0 for UP; 1 for DOWN.
required: false
default: false
type: boolean
invert_position:
description: Set this to true
if your actuator reports fully closed position as 0% in KNX.
required: false
default: false
type: boolean
invert_angle:
description: Set this to true
if your actuator reports fully closed tilt as 0% in KNX.
required: false
default: false
type: boolean
device_class:
description: Sets the class of the device, changing the device state and icon that is displayed on the frontend.
required: false
type: string
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Fan
The KNX fan integration is used to control KNX fans. Following control types are supported:
- Percentage controlled: Fans that set the percentage directly from 0-100%.
- Step controlled: Fans which have a fixed amount of steps to set. The integration will convert percentage to step automatically. The
max_step
attribute is set to the number of steps of the fan, not counting theoff
-step. Example: A fan supports the steps 0 to 3. To use this fan themax_step
attribute has to be set to3
. The integration will convert the percentage66 %
to the step2
when sending data to KNX.
To use your KNX fan in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
fan:
- name: "Ceiling fan"
address: "9/0/1"
state_address: "9/0/2"
{% configuration %} name: description: A name for this device used within Home Assistant. required: false type: string address: description: KNX group address for setting the percentage or step of the fan. DPT 5.001 or DPT 5.010 required: true type: [string, list] state_address: description: KNX group address for retrieving the percentage or step of the fan. DPT 5.001 or DPT 5.010 required: false type: [string, list] oscillation_address: description: KNX group address for switching the fan oscillation on or off. DPT 1 required: false type: [string, list] oscillation_state_address: description: KNX group address for retrieving the state of the fan oscillation. DPT 1 required: false type: [string, list] max_step: description: The maximum amount of steps for a step-controlled fan. If set, the integration will convert percentages to steps automatically. required: false type: integer entity_category: description: The category of the entity. required: false type: string default: None {% endconfiguration %}
Light
The KNX light integration is used as an interface to control KNX actuators for lighting applications such as:
- Switching actuators
- Dimming actuators
- LED controllers
- DALI gateways
To use your KNX light in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
light:
- name: "Kitchen"
address: "1/0/9"
{% configuration %}
address:
description: KNX group address for switching the light on and off. DPT 1.001
required: true
type: [string, list]
state_address:
description: KNX group address for retrieving the switch state of the light. DPT 1.001
required: false
type: [string, list]
name:
description: A name for this device used within Home Assistant.
required: false
type: string
brightness_address:
description: KNX group address for setting the brightness of the light in percent (absolute dimming). DPT 5.001
required: false
type: [string, list]
brightness_state_address:
description: KNX group address for retrieving the brightness of the light in percent. DPT 5.001
required: false
type: [string, list]
color_address:
description: KNX group address for setting the RGB color of the light. DPT 232.600
required: false
type: [string, list]
color_state_address:
description: KNX group address for retrieving the RGB color of the light. DPT 232.600
required: false
type: [string, list]
rgbw_address:
description: KNX group address for setting the RGBW color of the light. DPT 251.600
required: false
type: [string, list]
rgbw_state_address:
description: KNX group address for retrieving the RGBW color of the light. DPT 251.600
required: false
type: [string, list]
hue_address:
description: KNX group address for setting the hue of the light color in degrees. DPT 5.003
required: false
type: [string, list]
hue_state_address:
description: KNX group address for retrieving the hue of the light color in degrees. DPT 5.003
required: false
type: [string, list]
saturation_address:
description: KNX group address for setting the saturation of the light color in percent. DPT 5.001
required: false
type: [string, list]
saturation_state_address:
description: KNX group address for retrieving the saturation of the light color in percent. DPT 5.001
required: false
type: [string, list]
xyy_address:
description: KNX group address for setting the xyY color of the light. DPT 242.600
required: false
type: [string, list]
xyy_state_address:
description: KNX group address for retrieving the xyY color of the light. DPT 242.600
required: false
type: [string, list]
individual_colors:
description: Used when the actuator only supports individual group addresses for colors. When individual_colors
is used the root address
key may be omitted.
required: false
type: map
keys:
red:
description: Group addresses for the red component.
type: map
required: true
keys:
address:
description: KNX group address to switch the red component. DPT 1.001
type: [string, list]
required: false
state_address:
description: KNX group address for the state of the red component. DPT 1.001
type: [string, list]
required: false
brightness_address:
description: KNX group address to set the brightness of the red component. DPT 5.001
type: [string, list]
required: true
brightness_state_address:
description: KNX group address for the current brightness of the red component. DPT 5.001
type: [string, list]
required: false
green:
description: Group addresses for the green component. Same keys available as for red component above.
type: map
required: true
blue:
description: Group addresses for the blue component. Same keys available as for red component above.
type: map
required: true
white:
description: Group addresses for the white component. Same keys available as for red component above.
type: map
required: false
color_temperature_address:
description: KNX group address for setting the color temperature of the light. DPT 5.001 or 7.600 based on color_temperature_mode
required: false
type: [string, list]
color_temperature_state_address:
description: KNX group address for retrieving the color temperature of the light. DPT 5.001 or 7.600 based on color_temperature_mode
required: false
type: [string, list]
color_temperature_mode:
description: Color temperature group address data type. absolute
color temperature in Kelvin. color_temperature_address -> DPT 7.600. relative
color temperature in percent cold white (0% warmest; 100% coldest). color_temperature_address -> DPT 5.001
required: false
type: string
default: absolute
min_kelvin:
description: Warmest possible color temperature in Kelvin. Used in combination with color_temperature_address
.
required: false
type: integer
default: 2700
max_kelvin:
description: Coldest possible color temperature in Kelvin. Used in combination with color_temperature_address
.
required: false
type: integer
default: 6000
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Many KNX devices can change their state internally without a message to the switch address on the KNX bus, e.g., if you configure a scene or a timer on a channel. The optional state_address
can be used to inform Home Assistant about these state changes. If a KNX message is seen on the bus addressed to the given state_address
(in most cases from the light actuator), it will overwrite the state of the object.
For switching/light actuators that are only controlled by a single group address and don't have dedicated state group objects you can set state_address
to the same value as address
.
Note on tunable white: Home Assistant uses Mireds as the unit for color temperature, whereas KNX typically uses Kelvin. The Kelvin/Mireds relationship is reciprocal, not linear, therefore the color temperature pickers (sliders) in Home Assistant may not align with ones of KNX visualizations. This is the expected behavior.
Extended configuration examples
knx:
light:
# dimmable light
# color mode: brightness
- name: "Dimmable light"
address: "1/0/9"
state_address: "1/1/9"
brightness_address: "1/2/9"
brightness_state_address: "1/3/9"
# XYY light
# color mode: xy
- name: "XYY light"
address: "1/0/9"
state_address: "1/1/9"
brightness_address: "1/2/9" # optional - if not set brightness will be sent over the xyy data point
brightness_state_address: "1/3/9"
xyy_address: "1/4/9"
xyy_state_address: "1/5/9"
# HS light
# color mode: hs
- name: "HS light"
address: "1/0/9"
state_address: "1/1/9"
brightness_address: "1/2/9" # required for HS
brightness_state_address: "1/3/9"
hue_address: "1/4/8"
hue_state_address: "1/5/8" # required for HS
saturation_address: "1/4/9"
saturation_state_address: "1/5/9" # required for HS
# RGB light
# color mode: rgb
- name: "RGB light"
address: "1/0/9"
state_address: "1/1/9"
brightness_address: "1/2/9" # optional for RGB lights
brightness_state_address: "1/3/9"
color_address: "1/4/9"
color_state_address: "1/5/9"
# RGBW light
# color mode: rgbw
- name: "RGBW light"
address: "0/4/83"
state_address: "0/4/84"
brightness_address: "0/4/85" # optional for RGBW lights
brightness_state_address: "0/4/86"
rgbw_address: "0/4/87"
rgbw_state_address: "0/4/88"
# RGB(W) individual object light
# color mode: rgb / rgbw
- name: "RGBW individual light"
address: "1/0/9" # optional for individual color lights
individual_colors:
red:
brightness_address: "0/4/61"
brightness_state_address: "0/5/61"
green:
brightness_address: "0/4/62"
brightness_state_address: "0/5/62"
blue:
brightness_address: "0/4/63"
brightness_state_address: "0/5/63"
white:
brightness_address: "0/4/64"
brightness_state_address: "0/5/64"
# tunable white light
# color mode: color_temp
- name: "TW light"
address: "1/0/21"
state_address: "1/1/21"
brightness_address: "1/2/21"
brightness_state_address: "1/3/21"
color_temperature_address: "1/4/21"
color_temperature_state_address: "1/5/21"
color_temperature_mode: absolute
min_kelvin: 2550
max_kelvin: 6200
# actuator without dedicated state group object
# color mode: onoff
- name: "Simple light"
address: "1/0/5"
state_address: "1/0/5"
Notify
The KNX notify platform allows you to send notifications to KNX devices as DPT16 strings.
knx:
notify:
- name: "Alarm"
address: "5/1/10"
{% configuration %} address: description: KNX group address of the notification. DPT 16.000 required: true type: [string, list] name: description: A name for this device used within Home Assistant. required: false type: string type: description: A DPT identifier representing a text value ("string" or "latin_1" - see KNX Sensor) used to encode the notification. required: false default: "latin_1" type: string {% endconfiguration %}
Number
The KNX number platform allows to send generic numeric values to the KNX bus and update its state from received telegrams. It can optionally respond to read requests from the KNX bus with its current state.
Number entities without a state_address
will restore their last known state after Home Assistant was restarted.
Numbers having a state_address
configured request their current state from the KNX bus.
# Example configuration.yaml entry
knx:
number:
- name: "Duration"
address: "0/0/1"
type: time_period_sec
- name: "Volume"
address: "0/0/2"
state_address: "0/0/3"
type: percent
- name: "Temperature threshold"
address: "0/0/4"
respond_to_read: true
type: temperature
min: 20
max: 24.5
step: 0.1
mode: slider
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
type: string
address:
description: Group address new values will be sent to.
required: true
type: [string, list]
state_address:
description: Group address for retrieving the state from the KNX bus.
required: false
type: [string, list]
type:
description: Any supported type of KNX Sensor representing a numeric value (e.g., "percent" or "temperature").
required: true
type: [string, integer]
respond_to_read:
description: Respond to GroupValueRead telegrams received to the configured address
.
required: false
type: boolean
default: false
min:
description: Minimum value that can be sent. Defaults to the type
DPT minimum value.
required: false
type: float
max:
description: Maximum value that can be sent. Defaults to the type
DPT maximum value.
required: false
type: float
step:
description: Step value. Defaults to the step size defined for the DPT in the KNX specifications.
required: false
type: float
mode:
description: Specifies the mode used in the UI. auto
, box
or slider
are valid.
required: false
type: string
default: auto
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Scene
The KNX scenes platform allows you to trigger KNX scenes. These entities are write-only.
# Example configuration.yaml entry
knx:
scene:
- name: "Romantic"
address: 8/8/8
scene_number: 23
{% configuration %} address: description: KNX group address for the scene. DPT 17.001 required: true type: [string, list] scene_number: description: KNX scene number to be activated (range 1..64 ). required: true type: integer name: description: A name for this device used within Home Assistant. required: false type: string entity_category: description: The category of the entity. required: false type: string default: None {% endconfiguration %}
Select
The KNX select platform allows the user to define a list of values that can be selected via the frontend and can be used within conditions of automation. When a user selects a new item, the assigned generic raw payload is sent to the KNX bus. A received telegram updates the state of the select entity. It can optionally respond to read requests from the KNX bus with its current state.
Select entities without a state_address
will restore their last known state after Home Assistant was restarted.
Selects having a state_address
configured request their current state from the KNX bus.
# Example configuration.yaml entry
knx:
select:
- name: "DPT 2 selector"
address: "0/0/1"
payload_length: 0
options:
- option: "No control"
payload: 0
- option: "Control On"
payload: 0b10
- option: "Control Off"
payload: 0b11
- name: "DHWMode"
address: "0/0/2"
state_address: "0/0/3"
payload_length: 1
options:
- option: "Auto"
payload: 0
- option: "LegioProtect"
payload: 1
- option: "Normal"
payload: 2
- option: "Reduced"
payload: 3
- option: "Off/FrostProtect"
payload: 4
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
type: string
address:
description: Group address new values will be sent to.
required: true
type: [string, list]
state_address:
description: Group address for retrieving the state from the KNX bus.
required: false
type: [string, list]
payload_length:
description: The length of the payload expected for the DPT. Use 0
for DPT 1, 2 or 3.
required: true
type: integer
options:
description: List of options to choose from. Each option
and payload
have to be unique.
type: list
required: true
keys:
option:
description: The name of the option used to trigger the assigned payload
.
required: true
type: string
payload:
description: The raw payload assigned to the option
.
required: true
type: integer
respond_to_read:
description: Respond to GroupValueRead telegrams received to the configured address
.
required: false
type: boolean
default: false
sync_state:
description: Actively read the value from the bus. If false
no GroupValueRead telegrams will be sent to the bus. sync_state
can be set to init
to just initialize state on startup, expire <minutes>
to read the state from the KNX bus when no telegram was received for <minutes> or every <minutes>
to update it regularly every <minutes>. Maximum value for <minutes> is 1440. If just a number is configured "expire"-behaviour is used. Defaults to true
which is interpreted as "expire 60".
required: false
type: [boolean, string, integer]
default: true
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Sensor
The KNX sensor platform allows you to monitor KNX sensors.
Sensors are read-only. To write to the KNX bus configure a Number, an exposure KNX Integration Expose or use the knx.send
service.
# Example configuration.yaml entry
knx:
sensor:
- name: "Heating Valve 1"
state_address: "2/0/0"
type: percent
In order to actively read the sensor data from the bus every 30 minutes you can add the following lines to your configuration.yaml
:
# Example configuration.yaml entry
knx:
sensor:
- name: "Heating Valve 1"
state_address: "2/0/0"
type: percent
sync_state: every 30
{% configuration %}
state_address:
description: KNX group address of the sensor.
required: true
type: [string, list]
type:
description: A type from the value types table below must be defined. The DPT of the group address should match the expected KNX DPT to be parsed correctly.
required: true
type: [string, integer]
name:
description: A name for this device used within Home Assistant.
required: false
type: string
sync_state:
description: Actively read the value from the bus. If false
no GroupValueRead telegrams will be sent to the bus. sync_state
can be set to init
to just initialize state on startup, expire <minutes>
to read the state from the KNX bus when no telegram was received for <minutes> or every <minutes>
to update it regularly every <minutes>. Maximum value for <minutes> is 1440. If just a number is configured "expire"-behaviour is used. Defaults to true
which is interpreted as "expire 60".
required: false
type: [boolean, string, integer]
default: true
always_callback:
description: Defines if telegrams with equal payload as the previously received telegram should trigger a state update within Home Assistant.
required: false
type: boolean
default: false
state_class:
description: Sets the state_class of the sensor.
required: false
type: string
entity_category:
description: The category of the entity.
required: false
type: string
default: None
device_class:
description: Overrides the class of the device, changing the device state and icon that is displayed on the frontend.
required: false
type: string
{% endconfiguration %}
Value Types
KNX DPT | type | size in byte | range | unit |
---|---|---|---|---|
5 | 1byte_unsigned | 1 | 0 ... 255 | |
5.001 | percent | 1 | 0 ... 100 | % |
5.003 | angle | 1 | 0 ... 360 | ° |
5.004 | percentU8 | 1 | 0 ... 255 | % |
5.005 | decimal_factor | 1 | 0 ... 255 | |
5.006 | tariff | 1 | 0 ... 254 | |
5.010 | pulse | 1 | 0 ... 255 | counter pulses |
6 | 1byte_signed | 1 | -128 ... 127 | |
6.001 | percentV8 | 1 | -128 ... 127 | % |
6.010 | counter_pulses | 1 | -128 ... 127 | counter pulses |
7 | 2byte_unsigned | 2 | 0 ... 65535 | |
7.001 | pulse_2byte | 2 | 0 ... 65535 | pulses |
7.002 | time_period_msec | 2 | 0 ... 65535 | ms |
7.003 | time_period_10msec | 2 | 0 ... 65535 | ms |
7.004 | time_period_100msec | 2 | 0 ... 65535 | ms |
7.005 | time_period_sec | 2 | 0 ... 65535 | s |
7.006 | time_period_min | 2 | 0 ... 65535 | min |
7.007 | time_period_hrs | 2 | 0 ... 65535 | h |
7.011 | length_mm | 2 | 0 ... 65535 | mm |
7.012 | current | 2 | 0 ... 65535 | mA |
7.013 | brightness | 2 | 0 ... 65535 | lx |
7.600 | color_temperature | 2 | 0 ... 65535 | K |
8 | 2byte_signed | 2 | -32768 ... 32767 | |
8.001 | pulse_2byte_signed | 2 | -32768 ... 32767 | pulses |
8.002 | delta_time_ms | 2 | -32768 ... 32767 | ms |
8.003 | delta_time_10ms | 2 | -32768 ... 32767 | ms |
8.004 | delta_time_100ms | 2 | -32768 ... 32767 | ms |
8.005 | delta_time_sec | 2 | -32768 ... 32767 | s |
8.006 | delta_time_min | 2 | -32768 ... 32767 | min |
8.007 | delta_time_hrs | 2 | -32768 ... 32767 | h |
8.010 | percentV16 | 2 | -32768 ... 32767 | % |
8.011 | rotation_angle | 2 | -32768 ... 32767 | ° |
8.012 | length_m | 2 | -32768 ... 32767 | m |
9 | 2byte_float | 2 | -671088.64 ... 670760.96 | |
9.001 | temperature | 2 | -273 ... 670760 | °C |
9.002 | temperature_difference_2byte | 2 | -670760 ... 670760 | K |
9.003 | temperature_a | 2 | -670760 ... 670760 | K/h |
9.004 | illuminance | 2 | 0 ... 670760 | lx |
9.005 | wind_speed_ms | 2 | 0 ... 670760 | m/s |
9.006 | pressure_2byte | 2 | 0 ... 670760 | Pa |
9.007 | humidity | 2 | 0 ... 670760 | % |
9.008 | ppm | 2 | -671088.64 ... 670760.96 | ppm |
9.009 | air_flow | 2 | -671088.64 ... 670760.96 | m³/h |
9.010 | time_1 | 2 | -670760 ... 670760 | s |
9.011 | time_2 | 2 | -670760 ... 670760 | ms |
9.020 | voltage | 2 | -671088.64 ... 670760.96 | mV |
9.021 | curr | 2 | -671088.64 ... 670760.96 | mA |
9.022 | power_density | 2 | -671088.64 ... 670760.96 | W/m² |
9.023 | kelvin_per_percent | 2 | -671088.64 ... 670760.96 | K/% |
9.024 | power_2byte | 2 | -671088.64 ... 670760.96 | kW |
9.025 | volume_flow | 2 | -671088.64 ... 670760.96 | l/h |
9.026 | rain_amount | 2 | -671088.64 ... 670760.96 | l/m² |
9.027 | temperature_f | 2 | -459.6 ... 670760 | °F |
9.028 | wind_speed_kmh | 2 | 0 ... 670760 | km/h |
9.029 | absolute_humidity | 2 | 0 ... 670760 | g/m³ |
9.030 | concentration_ugm3 | 2 | 0 ... 670760 | μg/m³ |
9.? | enthalpy | 2 | -671088.64 ... 670760.96 | H |
12 | 4byte_unsigned | 4 | 0 ... 4294967295 | |
12.001 | pulse_4_ucount | 4 | 0 ... 4294967295 | counter pulses |
12.100 | long_time_period_sec | 4 | 0 ... 4294967295 | s |
12.101 | long_time_period_min | 4 | 0 ... 4294967295 | min |
12.100 | long_time_period_hrs | 4 | 0 ... 4294967295 | h |
12.1200 | volume_liquid_litre | 4 | 0 ... 4294967295 | l |
12.1201 | volume_m3 | 4 | 0 ... 4294967295 | m³ |
13 | 4byte_signed | 4 | -2147483648 ... 2147483647 | |
13.001 | pulse_4byte | 4 | -2147483648 ... 2147483647 | counter pulses |
13.002 | flow_rate_m3h | 4 | -2147483648 ... 2147483647 | m³/h |
13.010 | active_energy | 4 | -2147483648 ... 2147483647 | Wh |
13.011 | apparant_energy | 4 | -2147483648 ... 2147483647 | VAh |
13.012 | reactive_energy | 4 | -2147483648 ... 2147483647 | VARh |
13.013 | active_energy_kwh | 4 | -2147483648 ... 2147483647 | kWh |
13.014 | apparant_energy_kvah | 4 | -2147483648 ... 2147483647 | kVAh |
13.015 | reactive_energy_kvarh | 4 | -2147483648 ... 2147483647 | kVARh |
13.016 | active_energy_mwh | 4 | -2147483648 ... 2147483647 | MWh |
13.100 | long_delta_timesec | 4 | -2147483648 ... 2147483647 | s |
14 | 4byte_float | 4 | ||
14.000 | acceleration | 4 | m/s² | |
14.001 | acceleration_angular | 4 | rad/s² | |
14.002 | activation_energy | 4 | J/mol | |
14.003 | activity | 4 | s⁻¹ | |
14.004 | mol | 4 | mol | |
14.005 | amplitude | 4 | ||
14.006 | angle_rad | 4 | rad | |
14.007 | angle_deg | 4 | ° | |
14.008 | angular_momentum | 4 | J s | |
14.009 | angular_velocity | 4 | rad/s | |
14.010 | area | 4 | m² | |
14.011 | capacitance | 4 | F | |
14.012 | charge_density_surface | 4 | C/m² | |
14.013 | charge_density_volume | 4 | C/m³ | |
14.014 | compressibility | 4 | m²/N | |
14.015 | conductance | 4 | S | |
14.016 | electrical_conductivity | 4 | S/m | |
14.017 | density | 4 | kg/m³ | |
14.018 | electric_charge | 4 | C | |
14.019 | electric_current | 4 | A | |
14.020 | electric_current_density | 4 | A/m² | |
14.021 | electric_dipole_moment | 4 | C m | |
14.022 | electric_displacement | 4 | C/m² | |
14.023 | electric_field_strength | 4 | V/m | |
14.024 | electric_flux | 4 | c | |
14.025 | electric_flux_density | 4 | C/m² | |
14.026 | electric_polarization | 4 | C/m² | |
14.027 | electric_potential | 4 | V | |
14.028 | electric_potential_difference | 4 | V | |
14.029 | electromagnetic_moment | 4 | A m² | |
14.030 | electromotive_force | 4 | V | |
14.031 | energy | 4 | J | |
14.032 | force | 4 | N | |
14.033 | frequency | 4 | Hz | |
14.034 | angular_frequency | 4 | rad/s | |
14.035 | heatcapacity | 4 | J/K | |
14.036 | heatflowrate | 4 | W | |
14.037 | heat_quantity | 4 | J | |
14.038 | impedance | 4 | Ω | |
14.039 | length | 4 | m | |
14.040 | light_quantity | 4 | lm s | |
14.041 | luminance | 4 | cd/m² | |
14.042 | luminous_flux | 4 | lm | |
14.043 | luminous_intensity | 4 | cd | |
14.044 | magnetic_field_strength | 4 | A/m | |
14.045 | magnetic_flux | 4 | Wb | |
14.046 | magnetic_flux_density | 4 | T | |
14.047 | magnetic_moment | 4 | A m² | |
14.048 | magnetic_polarization | 4 | T | |
14.049 | magnetization | 4 | A/m | |
14.050 | magnetomotive_force | 4 | A | |
14.051 | mass | 4 | kg | |
14.052 | mass_flux | 4 | kg/s | |
14.053 | momentum | 4 | N/s | |
14.054 | phaseanglerad | 4 | rad | |
14.055 | phaseangledeg | 4 | ° | |
14.056 | power | 4 | W | |
14.057 | powerfactor | 4 | ||
14.058 | pressure | 4 | Pa | |
14.059 | reactance | 4 | Ω | |
14.060 | resistance | 4 | Ω | |
14.061 | resistivity | 4 | Ωm | |
14.062 | self_inductance | 4 | H | |
14.063 | solid_angle | 4 | sr | |
14.064 | sound_intensity | 4 | W/m² | |
14.065 | speed | 4 | m/s | |
14.066 | stress | 4 | Pa | |
14.067 | surface_tension | 4 | N/m | |
14.068 | common_temperature | 4 | °C | |
14.069 | absolute_temperature | 4 | K | |
14.070 | temperature_difference | 4 | K | |
14.071 | thermal_capacity | 4 | J/K | |
14.072 | thermal_conductivity | 4 | W/mK | |
14.073 | thermoelectric_power | 4 | V/K | |
14.074 | time_seconds | 4 | s | |
14.075 | torque | 4 | Nm | |
14.076 | volume | 4 | m³ | |
14.077 | volume_flux | 4 | m³/s | |
14.078 | weight | 4 | N | |
14.079 | work | 4 | J | |
14.080 | apparent_power | 4 | VA | |
16.000 | string | 14 | ASCII | |
16.001 | latin_1 | 14 | ISO 8859-1 / Latin-1 | |
17.001 | scene_number | 1 | 1 ... 64 |
More examples
# Example configuration.yaml entry
knx:
sensor:
- name: "Heating Valve 1"
state_address: "2/0/0"
sync_state: init
type: percent
- name: "Kitchen Temperature"
state_address: "6/2/1"
sync_state: every 60
type: temperature
state_class: measurement
Switch
The KNX switch platform is used as an interface to switching actuators.
knx:
switch:
- name: "Kitchen coffee maker"
address: "1/1/6"
{% configuration %}
address:
description: KNX group address for switching the switch on/off. DPT 1
required: true
type: [string, list]
name:
description: A name for this device used within Home Assistant.
required: false
default: KNX Switch
type: string
state_address:
description: Separate KNX group address for retrieving the switch state. DPT 1
required: false
type: [string, list]
invert:
description: Invert the telegrams payload before processing or sending.
required: false
type: boolean
default: false
respond_to_read:
description: Respond to GroupValueRead telegrams received to the configured address
.
required: false
type: boolean
default: false
entity_category:
description: The category of the entity.
required: false
type: string
default: None
device_class:
description: Sets the class of the device, changing the device state and icon that is displayed on the frontend.
required: false
type: string
{% endconfiguration %}
The optional state_address
can be used to inform Home Assistant about state changes not triggered by a telegram to the address
e.g., if you configure a timer on a channel. If a KNX message is seen on the bus addressed to the given state address, this will overwrite the state of the switch object.
Switch entities without a state_address
will restore their last known state after Home Assistant was restarted.
Switches having a state_address
configured request their current state from the KNX bus.
Text
The KNX text platform allows to send text values to the KNX bus and update its state from received telegrams. It can optionally respond to read requests from the KNX bus with its current state.
Text entities without a state_address
will restore their last known state after Home Assistant was restarted.
Texts having a state_address
configured request their current state from the KNX bus.
# Example configuration.yaml entry
knx:
text:
- name: "Info"
address: "0/0/1"
- name: "ASCII Info"
address: "0/0/2"
state_address: "0/0/3"
type: string
- name: "Greeting"
address: "0/0/4"
respond_to_read: true
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
type: string
address:
description: Group address new values will be sent to.
required: true
type: [string, list]
state_address:
description: Group address for retrieving the state from the KNX bus.
required: false
type: [string, list]
type:
description: Either latin_1
for DPT 16.001 or string
for DPT 16.000 (ASCII).
required: false
type: [string, integer]
default: latin_1
respond_to_read:
description: Respond to GroupValueRead telegrams received to the configured address
.
required: false
type: boolean
default: false
mode:
description: Specifies the mode used in the UI. text
or password
are valid.
required: false
type: string
default: text
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Weather
The KNX weather platform is used as an interface to KNX weather stations.
To use your KNX weather station in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
weather:
- name: "Home"
address_temperature: "7/0/0"
address_brightness_south: "7/0/1"
address_brightness_west: "7/0/2"
address_brightness_east: "7/0/3"
address_brightness_north: "7/0/11"
address_wind_speed: "7/0/4"
address_rain_alarm: "7/0/5"
address_frost_alarm: "7/0/6"
address_wind_alarm: "7/0/7"
address_day_night: "7/0/8"
address_air_pressure: "7/0/9"
address_humidity: "7/0/10"
sync_state: true
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
default: KNX Weather
type: string
address_temperature:
description: KNX group address for reading current outside temperature from KNX bus. DPT 9.001
required: true
type: [string, list]
address_brightness_south:
description: KNX group address for reading current brightness to south coordinate from KNX bus. DPT 9.004
required: false
type: [string, list]
address_brightness_west:
description: KNX group address for reading current brightness to west coordinate from KNX bus. DPT 9.004
required: false
type: [string, list]
address_brightness_east:
description: KNX group address for reading current brightness to east coordinate from KNX bus. DPT 9.004
required: false
type: [string, list]
address_brightness_north:
description: KNX group address for reading current brightness to north coordinate from KNX bus. DPT 9.004
required: false
type: [string, list]
address_wind_bearing:
description: KNX group address for reading current wind bearing from KNX bus. DPT 5.003
required: false
type: [string, list]
address_wind_speed:
description: KNX group address for reading current wind speed from KNX bus. DPT 9.005
required: false
type: [string, list]
address_rain_alarm:
description: KNX group address for reading if rain alarm is on/off.
required: false
type: [string, list]
address_frost_alarm:
description: KNX group address for reading if frost alarm is on/off.
required: false
type: [string, list]
address_wind_alarm:
description: KNX group address for reading if wind alarm is on/off.
required: false
type: [string, list]
address_day_night:
description: KNX group address for reading if it's day/night.
required: false
type: [string, list]
address_air_pressure:
description: KNX address reading current air pressure. DPT 9.006
required: false
type: [string, list]
address_humidity:
description: KNX address for reading current humidity. DPT 9.007
required: false
type: [string, list]
sync_state:
description: Actively read the value from the bus. If false
no GroupValueRead telegrams will be sent to the bus.
required: false
type: boolean
default: true
entity_category:
description: The category of the entity.
required: false
type: string
default: None
{% endconfiguration %}
Troubleshooting / Common issues
Logs for the KNX integration
xknx
, the library used for KNX communication, provides various logging handlers for monitoring and debug purposes.
Add the following lines to your Home Assistant configuration.yaml
to activate them:
logger:
default: warning
logs:
# For most debugging needs `xnx.log` and `xknx.telegram` are a good choice.
xknx: info # sets the level of all loggers
# Loggers for different layers of KNX communication
xknx.log: debug # provides general information (connection, etc.)
xknx.telegram: debug # logs telegrams before they are being processed or sent
xknx.cemi: debug # logs incoming and outgoing CEMI frames
xknx.data_secure: debug # logs Data Secure relevant information
xknx.ip_secure: debug # logs IP Secure relevant information
xknx.knx: debug # logs incoming and outgoing KNX/IP frames
xknx.raw_socket: warning # logs incoming UDP/TCP frames in raw hex format at socket level
# Loggers for xknx internals
xknx.state_updater: warning # provides information about the state updater
You can use the service logger.set_level
to change the log level of a handler on a running instance.
{% my developer_call_service badge service="logger.set_level" %}
Group address can not be read
Every *_state_address
is read on startup sequentially if not configured differently. If you see the following errors in your log, a group address could not be read by a GroupValueRead request from Home Assistant in time.
> Could not sync group address '1/2/3' (Entity name - Feature)
> Error: KNX bus did not respond in time (2.0 secs) to GroupValueRead request for: '1/2/3'
No group object (GO) assigned to the group address (GA) has the Read-Flag set in ETS
- Enable the read flag for one GO assigned to the GA. Use the one most likely to hold the current state (e.g., for a light entity's
brightness_state_address
the according GO of the dimming actuator).
Response telegrams are not passing a line coupler, router or other filter in the installation
- Assign the group addresses used by Home Assistant to the used interface in ETS if your interface application supports that. ETS will generate filter tables that are applied to your line couplers after updating their application.
- If your interface application doesn't support that, use a dummy device in ETS for Home Assistant. These can be found in the ETS online catalog. Assign it to the line your interface connects Home Assistant to and link its group objects to the group addresses you are using in Home Assistant.
Unresponsive system
- The timeout for logging the errors (2 seconds) is started when the GroupValueRead request is scheduled to be sent. On systems experiencing high loads sending can be delayed (e.g., Raspberry Pi running lots of integrations at startup). Incoming response telegrams are always processed, so no information gets lost.
Duplicate entities
If you find following error in your log you seem to have a duplicated entity in your configuration.
Platform knx does not generate unique IDs. ID 1/2/3 already exists - ignoring platform.name
The unique_id
for KNX entities is generated based on required configuration values.
- binary_sensor:
state_address
- climate:
temperature_address
target_temperature_state_address
target_temperature_address
setpoint_shift_address
- cover:
move_long_address
position_address
- fan:
address
- light:
address
or all combinedbrightness_address
if onlyindividual_colors
is used - notify:
address
- scene:
address
andscene_number
- sensor:
state_address
- switch:
address
- weather:
address_temperature