Modbus is a serial communication protocol to control PLCs (Programmable Logic Controller). It supports various types of devices which can be controlled over serial, TCP, and UDP connections.
Configuration
How to add modbus to your installation depends on the connection type, either a network or serial connection.
Platforms:
- binary_sensor
- climate
- cover
- sensor
- switch
are all defined as part of the modbus configuration. The old configuration style, (having each outside the modbus configuration is still supported, but will cause a warning, and will be removed in a later release).
Network connection
For a network connection, add the following to your configuration.yaml
file:
# Example configuration.yaml entry for a TCP connection
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
{% configuration %}
delay:
description: Time to sleep in seconds after connecting and before sending messages. Some modbus-tcp servers need a short delay typically 1-2 seconds in order to prepare the communication. If a server accepts connecting, but there is no response to the requests send, this parameter might help.
required: false
default: 0
type: integer
host:
description: The IP address of your Modbus device, e.g., 192.168.1.1.
required: true
type: string
name:
description: Name for this hub. Must be unique, so it is required when setting up multiple instances.
required: false
default: modbus_hub
type: string
port:
description: The network port for the communication.
required: true
type: integer
timeout:
description: Timeout for slave response in seconds.
required: false
default: 3
type: integer
type:
description: Type of the connection to Modbus. Possible values are tcp
(Modbus TCP protocol according to "MODBUS Messaging Implementation Guide version 1.0b" provided by Schneider Automation.), udp
(Modbus TCP form, but using UDP for transport. It removes the overheads required for TCP.) and rtuovertcp
(Modbus RTU message transmitted with a TCP/IP wrapper and sent over a network instead of serial lines.).
required: true
type: string
{% endconfiguration %}
Serial connection
For a serial connection, add the following to your configuration.yaml
file:
# Example configuration.yaml entry for a serial connection
modbus:
- name: hub1
type: serial
method: rtu
port: /dev/ttyUSB0
baudrate: 9600
stopbits: 1
bytesize: 8
parity: N
{% configuration %}
baudrate:
description: The speed for the serial connection.
required: true
type: integer
bytesize:
description: "The bytesize for the serial connection; can be 5
, 6
, 7
or 8
."
required: true
type: integer
delay:
description: Time to sleep in seconds after connecting and before sending messages. Some modbus servers need a short delay typically 1-2 seconds in order to prepare the communication. If a server accepts connecting, but there is no response to the requests send, this parameter might help.
required: false
default: 0
type: integer
method:
description: "Method of the connection to Modbus, either rtu
or ascii
."
required: true
type: string
name:
description: Name for this hub. Must be unique, so it is required when setting up multiple instances.
required: false
default: modbus_hub
type: string
parity:
description: "The parity for the serial connection; can be E
, O
or N
."
required: true
type: string
port:
description: The port where your Modbus device is connected to your Home Assistant host.
required: true
type: string
stopbits:
description: "The stopbits for the serial connection, either 1
or 2
."
required: true
type: integer
timeout:
description: Timeout for slave response in seconds.
required: false
default: 3
type: integer
type:
description: "Type of the connection to Modbus, needs to be serial
for this setup."
required: true
type: string
{% endconfiguration %}
Configuring platform binary sensor
The modbus
binary sensor allows you to gather data from Modbus coils with state ON/OFF.
To use your Modbus binary sensors in your installation, add the following to your configuration.yaml
file:
# Example configuration.yaml entry for binary_sensor configuration
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
binary_sensors:
- name: Sensor1
slave: 1
address: 100
- name: Sensor2
address: 110
input_type: discrete_input
{% configuration %} binary_sensors: description: A list of all binary_sensors available in this modbus instance. required: false type: [map] keys: device_class: description: Device class to be used for the UI (e.g. "door"). required: false type: string input_type: description: type of adddress (holding/discrete/coil) required: false default: holding type: integer name: description: Name for this binary_sensor. Must be unique. required: true type: string scan_interval: description: Defines the update interval of the sensor in seconds. required: false type: integer default: 15 slave: description: The number of the slave. required: false type: integer {% endconfiguration %}
Configuring platform climate
To use your Modbus thermostat in your installation, add the following to your configuration.yaml
file:
# Example configuration.yaml entry
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
climates:
- name: Watlow F4T
slave: 1
data_type: uint
data_count: 1
scale: 0.1
offset: 0
precision: 1
max_temp: 30
min_temp: 15
temp_step: 1
target_temp_register: 2782
current_temp_register: 27586
{% configuration %}
climates:
description: A list of all climates available in this modbus instance.
required: false
type: [map]
keys:
current_temp_register:
description: Register number for current temperature (Process value).
required: true
type: integer
current_temp_register_type:
description: Modbus register type (holding, input) for current temperature, default holding.
required: false
type: string
default: holding
data_count:
description: Number of registers to read.
required: false
type: integer
default: 2
data_type:
description: Response representation (int, uint, float, custom). If float selected, value will converted to IEEE 754 floating point format.
required: false
type: string
default: float
min_temp:
description: Maximum setpoint temperature.
required: false
type: integer
default: 5
name:
description: Name of the device
required: true
type: string
offset:
description: Final offset (output = scale * value + offset).
required: false
type: float
default: 0
precision:
description: Number of valid decimals.
required: false
type: integer
default: 1
scale:
description: Scale factor (output = scale * value + offset).
required: false
type: float
default: 1
scan_interval:
description: Defines the update interval of the sensor in seconds.
required: false
type: integer
default: 15
slave:
description: The number of the slave (Optional for tcp and upd Modbus, use 1).
required: true
type: integer
structure:
description: "If data_type
is custom specified a double-quoted Python struct is expected here, to format the string to unpack the value. See Python documentation for details. Example: >i
."
required: false
type: string
default: ">f"
target_temp_register:
description: Register number for target temperature (Setpoint).
required: true
type: integer
temp_step:
description: The supported step size a target temperature can be increased/decreased.
required: false
type: float
default: 0.5
temperature_unit:
description: Temperature unit reported by the current_temp_register. C or F
required: false
type: string
default: C
{% endconfiguration %}
Services
Service | Description |
---|---|
set_temperature | Set Temperature. Requires value to be passed in, which is the desired target temperature. value should be in the same type as data_type |
Configuring platform cover
The modbus
cover platform allows you to control Modbus covers (such as blinds, a roller shutter, or a garage door).
At the moment, we support the opening and closing of a cover. You can control your covers either using coils or holding registers.
Cover that uses the coil
attribute is not able to determine intermediary states such as opening and closing. Coil stores only two states — "0" means cover closed, and "1" implies cover open. To allow detecting intermediary states, we added an optional status_register
attribute. It will enable you to write your command (e.g., to open a cover) into a coil, and read current cover status back through the register. Additionally, you can specify values for state_open
, state_opening
, state_closed
, and state_closing
attributes. These will be matched with the value read from the status_register
.
If your cover uses holding register to send commands (defined by the register
attribute), it can also read the intermediary states. To adjust which value represents what state, you can fine-tune the optional state attributes, like state_open
. These optional state values are also used for specifying values written into the register. If you specify an optional status_register attribute, cover states will be read from status_register instead of the register used for sending commands.
To use Modbus covers in your installation, add the following to your configuration.yaml
file:
# Example configuration.yaml entry
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
covers:
- name: Door1
device_class: door
scan_interval: 1
coil: 0
- name: Door2
device_class: door
scan_interval: 1
coil: 1
status_register: 1
- name: Door3
slave: 2
device_class: door
scan_interval: 1
register: 0
state_open: 1
state_closed: 0
{% configuration %}
covers:
description: The array contains a list of all your Modbus covers.
required: true
type: map
keys:
coil:
description: Coil address; can be omitted if a register attribute is specified. Coil and register attributes are mutually exclusive, and you need to always specify one of them.
required: true
type: integer
device_class:
description: The type/class of the cover to set the icon in the frontend.
required: false
type: device_class
default: None
name:
description: Name of the switch.
required: true
type: string
register:
description: Holding register address; can be omitted if a coil attribute is specified. Coil and register attributes are mutually exclusive, and you need to always specify one of them.
required: true
type: integer
scan_interval:
description: Defines the update interval of the sensor in seconds.
required: false
type: integer
default: 15
slave:
description: The number of the slave (can be omitted for tcp and udp Modbus).
required: false
default: 1
type: integer
state_open:
description: A value in status_register
or register
representing an open cover. If your configuration uses an register
attribute, this value will be also written into a holding register to open the cover.
required: false
default: 1
type: integer
state_closed:
description: A value in status_register
or register
representing a closed cover. If your configuration uses an register
attribute, this value will be also written into a holding register to close the cover.
required: false
default: 0
type: integer
state_opening:
description: A value in status_register
or register
telling us that the cover is opening at the moment. Note that this state should be also supported on your connected Modbus cover. If it won't write this intermediary state into the register, this state won't be detected.
required: false
default: 2
type: integer
state_closing:
description: A value in status_register
or register
telling us that the cover is closing at the moment. Note that this state should be also supported on your connected Modbus cover. If it won't write this intermediary state into the register, this state won't be detected.
required: false
default: 2
type: integer
status_register:
description: An address of an register, from which all the cover states will be read. If you specified register
attribute, and not status_register
attribute, your main register will also be used as a status register.
required: false
type: integer
status_register_type:
description: Modbus register type (holding, input), default holding.
required: false
type: string
{% endconfiguration %}
Example: Modbus cover controlled by a coil
This example shows a configuration for a Modbus cover controlled using a coil. Intermediary states like opening/closing are not supported. The cover state is polled from Modbus every 10 seconds.
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
covers:
- name: Door1
slave: 1
coil: 1
device_class: door
scan_interval: 10
- name: Door2
slave: 2
coil: 2
device_class: door
scan_interval: 10
Example: Modbus cover controlled by a coil, it's state is read from the register
This example shows a configuration for a Modbus cover controlled using a coil. Actual cover state is read from the status_register
. We've also specified register values to match with the states open/opening/closed/closing. The cover state is polled from Modbus every 10 seconds.
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
covers:
- name: Door1
slave: 1
device_class: door
scan_interval: 10
coil: 1
status_register: 1
status_register_type: input
state_opening: 1
state_open: 2
state_closing: 3
state_closed: 4
Example: Modbus cover controlled by a holding register
This example shows a configuration for a Modbus cover controlled using a holding register, from which we also read current cover state. We've also specified register values to match with the states open/opening/closed/closing. The cover state is polled from Modbus every 10 seconds.
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
covers:
- name: Door1
slave: 1
device_class: door
scan_interval: 10
register: 1
state_opening: 1
state_open: 2
state_closing: 3
state_closed: 4
Example: Modbus cover controlled by a holding register, it's state is read from the status register
This example shows a configuration for a Modbus cover controlled using a holding register. However, cover state is read from a status_register
. In this case, we've specified only values for state_open
and state_closed
, for the rest, default values are used. The cover state is polled from Modbus every 10 seconds.
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
covers:
- name: Door1
slave: 1
device_class: door
scan_interval: 10
register: 1
status_register: 2
register_type: holding
state_open: 1
state_closed: 0
Configuring platform sensor
The modbus
cover platform allows you to control Modbus covers (such as blinds, a roller shutter, or a garage door).
The modbus
sensor allows you to gather data from Modbus registers.
To use your Modbus sensors in your installation, add the following to your configuration.yaml
file:
# Example configuration.yaml entry
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
sensors:
- name: Sensor1
unit_of_measurement: °C
slave: 1
address: 100
- name: Sensor2
unit_of_measurement: mg
slave: 1
address: 110
count: 2
- name: Sensor3
unit_of_measurement: °C
slave: 1
address: 120
input_type: input
data_type: float
scale: 0.01
offset: -273.16
precision: 2
{% configuration %}
sensors:
description: The array contains a list of all your Modbus sensors.
required: true
type: map
keys:
address:
description: Register number.
required: true
type: integer
count:
description: Number of registers to read.
required: false
type: integer
default: 1
data_type:
description: Response representation (int, uint, float, string, custom). If float selected, value will be converted to IEEE 754 floating point format.
required: false
default: int
type: string
device_class:
description: The type/class of the sensor to set the icon in the frontend.
required: false
type: device_class
default: None
input_type:
description: Modbus register type (holding, input), default holding.
required: false
type: string
name:
description: Name of the sensor.
required: true
type: string
offset:
description: Final offset (output = scale * value + offset).
required: false
default: 0
type: float
precision:
description: Number of valid decimals.
required: false
default: 0
type: integer
reverse_order:
description: Reverse the order of registers when count >1.
required: false
default: false
type: boolean
scale:
description: Scale factor (output = scale * value + offset).
required: false
default: 1
type: float
scan_interval:
description: Defines the update interval of the sensor in seconds.
required: false
type: integer
default: 15
slave:
description: The number of the slave (Optional for tcp and upd Modbus).
required: true
type: integer
structure:
description: "If data_type
is custom specified a double-quoted Python struct is expected here, to format the string to unpack the value. See Python documentation for details. Example: >i
."
required: false
type: string
unit_of_measurement:
description: Unit to attach to value.
required: false
type: integer
{% endconfiguration %}
If you specify scale or offset as floating point values, double precision floating point arithmetic will be used to calculate final value. This can cause loss of precision for values that are larger than 2^53.
Full example
Example a temperature sensor with a 10 seconds scan interval:
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
sensors:
- name: Room_1
slave: 10
address: 0
input_type: holding
unit_of_measurement: °C
count: 1
scale: 0.1
offset: 0
precision: 1
data_type: integer
Configuring platform switch
The modbus
switch platform allows you to control Modbus coils or registers.
To use your Modbus switches in your installation, add the following to your configuration.yaml
file:
# Example configuration.yaml entry
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
switches:
- name: Switch1
address: 13
input_type: coil
- name: Switch2
slave: 2
address: 14
input_type: coil
- name: Register1
address: 11
command_on: 1
command_off: 0
{% configuration %} switches: description: The array contains a list of all your Modbus switches. required: true type: map keys: address: description: Coil number or register required: true type: integer command_on: description: Value to write to turn on the switch. required: true type: integer command_off: description: Value to write to turn off the switch. required: true type: integer input_type: description: type of adddress (holding/input/coil) required: false default: holding type: integer name: description: Name of the switch. required: true type: string scan_interval: description: Defines the update interval of the sensor in seconds. required: false type: integer default: 15 slave: description: The number of the slave (can be omitted for tcp and udp Modbus). required: true type: integer state_on: description: Register value when switch is on. required: false default: same as command_on type: integer state_off: description: Register value when switch is off. required: false default: same as command_off type: integer verify_register: description: Register to readback. required: false default: same as register type: string verify_state: description: Define if is possible to readback the status of the switch. required: false default: true type: boolean {% endconfiguration %}
Full example
Example switches, for which the state is polled from Modbus every 10 seconds.
modbus:
- name: hub1
type: tcp
host: IP_ADDRESS
port: 502
switches:
- name: Switch1
slave: 1
address: 13
input_type: coil
- name: Switch2
slave: 2
address: 14
Multiple connections
Multiple connections are possible, add something like the following to your configuration.yaml
file:
# Example configuration.yaml entry for multiple TCP connections
modbus:
- type: tcp
host: IP_ADDRESS_1
port: 2020
name: hub1
- type: tcp
host: IP_ADDRESS_2
port: 501
name: hub2
Services
Service | Description |
---|---|
write_register | Write register. Requires hub , unit , address and value fields. value can be either single value or an array |
Service Data Attributes
Attribute | Description |
---|---|
hub | Hub name (defaults to 'default' when omitted) |
unit | Slave address (1-255, mostly 255 if you talk to Modbus via TCP) |
address | Address of the Register (e.g., 138) |
value | A single value or an array of 16-bit values. Single value will call modbus function code 6. Array will call modbus function code 16. Array might need reverse ordering. E.g., to set 0x0004 you might need to set [4,0] |
Log warning (v1.0.8 and onwards)
Pymodbus (which is the implementation library) was updated and issues a warning:
- "Not Importing deprecated clients. Dependency Twisted is not Installed"
This warning can be safely ignored, and have no influence on how the integration works!
Opening an issue
When opening an issue, please add your current configuration (or a scaled down version), with at least:
- the Modbus configuration lines
- the entity (sensor, etc.) lines
In order for the developers better to identify the problem, please add the following lines to configuration.yaml:
logger:
logs:
homeassistant.components.modbus: debug
pymodbus.client: debug
and restart Home Assistant, reproduce the problem, and include the log in the issue.