49 KiB
title, description, ha_category, ha_release, ha_iot_class, ha_codeowners, ha_domain, ha_quality_scale
title | description | ha_category | ha_release | ha_iot_class | ha_codeowners | ha_domain | ha_quality_scale | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
KNX | Instructions on how to integrate KNX components with Home Assistant. |
|
0.24 | Local Push |
|
knx | silver |
The KNX integration for Home Assistant allows you to connect to KNX/IP devices.
The integration requires a local KNX/IP interface or router. Through this, it will establish a connection between Home Assistant and your KNX bus.
Please note, the knx
platform does not support KNX Secure.
There is currently support for the following device types within Home Assistant:
Basic Configuration
To use your KNX bus in your installation, add the following lines to your configuration.yaml
file:
knx:
In order to make use of the various platforms KNX offers you will need to have the following configuration inside configuration.yaml
depending on what
platforms you intend to use:
knx:
binary_sensor: !include knx_binary_sensor.yaml
switch: !include knx_switch.yaml
sensor: !include knx_sensor.yaml
cover: !include knx_cover.yaml
light: !include knx_light.yaml
notify: !include knx_notify.yaml
scene: !include knx_scene.yaml
Please check the dedicated platform documentation about how to configure them correctly.
Optional, or if you want to use the XKNX abstraction also for other scripted tools outside of Home Assistant:
knx:
config_file: '/path/to/xknx.yaml'
{% configuration %} config_file: description: The path for XKNX configuration file. See xknx.io for details required: false type: string rate_limit: description: Defines the maximum number of telegrams to be sent to the bus per second (range 1-100). required: false default: 20 type: integer individual_address: description: The KNX individual address that shall be used for routing or if a tunnelling server doesn't assign an IA at connection. required: false type: string default: "15.15.250" multicast_group: description: The multicast group to use for automatic interface discovery and routing communication. required: false type: string default: "224.0.23.12" multicast_port: description: The port for multicast communication. required: false type: integer default: 3671 {% endconfiguration %}
If the auto detection of the KNX/IP device does not work you can specify IP and port of the tunneling device:
knx:
tunneling:
host: '192.168.2.23'
port: 3671
local_ip: '192.168.2.109'
{% configuration %} host: description: IP address of the KNX/IP tunneling device. type: string required: true port: description: Port of the KNX/IP tunneling device. type: integer required: false local_ip: description: IP address of the local interface. type: string required: false {% endconfiguration %}
Explicit connection to a KNX/IP routing device:
knx:
routing:
local_ip: '192.168.2.109'
{% configuration %} local_ip: description: The local IP address of the interface that shall be used to send multicast packets. type: string required: true {% endconfiguration %}
knx:
fire_event: true
fire_event_filter: ["1/0/*", "6/2,3,4-6/*"]
{% configuration %}
fire_event:
description: If set to True, platform will write all received KNX messages to event bus
required: inclusive
type: boolean
default: false
fire_event_filter:
description: If fire_event
is set fire_event_filter
has to be specified. fire_event_filter
defines a list of patterns for filtering KNX addresses. Only telegrams which match this pattern are sent to the Home Assistant event bus.
required: inclusive
type: [list, string]
state_updater:
description: The integration will collect the current state of each configured device from the KNX bus to display it correctly within Home Assistant. Set this option to False to prevent this behavior.
required: false
default: true
type: boolean
{% endconfiguration %}
Services
In order to directly interact with the KNX bus, you can use the following service:
Domain: knx
Service: send
Service Data: {"address": "1/0/15", "payload": 0, "type": "temperature"}
{% configuration %}
address:
description: KNX group address
type: string
payload:
description: Payload to send to the bus. When type
is not set, raw bytes are sent. Integers are then treated as DPT 1/2/3 payloads. For DPTs > 6 bits send a list. Each value represents 1 octet (0-255). Pad with 0 to DPT byte length.
type: [integer, list]
type:
description: If set, the payload will not be sent as raw bytes, but encoded as given DPT. KNX sensor types are valid values - see table in KNX Sensor.
type: [string, integer, float]
{% endconfiguration %}
You can also use the homeassistant.update_entity
service call to issue GroupValueRead requests for all *state_address
of a device.
Exposing entity states, entity attributes or time to KNX bus
KNX integration is able to expose entity states or attributes to KNX bus. The integration will broadcast any change of the exposed value to the KNX bus and answer read requests to the specified group address. It is also possible to expose the current time.
# Example configuration.yaml entry
knx:
expose:
- type: 'temperature'
entity_id: 'sensor.owm_temperature'
address: '0/0/2'
- type: 'string'
address: '0/6/4'
entity_id: "sensor.owm_weather"
- type: 'binary'
entity_id: 'binary_sensor.kitchen_window'
address: '0/6/5'
- type: 'binary'
entity_id: 'light.office'
address: '0/3/0'
default: False
- type: 'percentU8'
entity_id: 'light.office'
attribute: 'brightness'
default: 0
address: '0/3/1'
- type: 'time'
address: '0/0/1'
- type: 'datetime'
address: '0/0/23'
{% configuration %}
type:
description: Type of the exposed value. Either 'binary', 'time', 'date', 'datetime' or any supported type of KNX Sensor (e.g., "temperature" or "humidity").
type: string
required: true
entity_id:
description: Entity id to be exposed. Not needed for types time, date and datetime.
type: string
required: false
attribute:
description: Attribute of the entity that shall be sent to the KNX bus. If not set (or None
) the state will be sent.
Eg. for a light the state is eigther "on" or "off" - with attribute you can expose its "brightness".
type: string
required: false
default:
description: Default value to send to the bus if the state or attribute value is None
.
Eg. a light with state "off" has no brightness attribute so a default value of 0
could be used.
If not set (or None
) no value would be sent to the bus and a GroupReadRequest to the address would return the last known value.
type: [boolean, string, integer, float]
default: None
required: false
address:
description: KNX group address.
type: string
required: true
{% endconfiguration %}
The knx
sensor platform allows you to monitor KNX binary sensors.
Binary sensors are read-only. To write to the knx-bus configure an exposure KNX Integration - Expose.
Binary Sensor
To use your binary sensors please add the relevant configuration to your top level KNX Integration configuration key in configuration.yaml
:
knx:
binary_sensor:
- name: sensor1
state_address: '6/0/2'
{% configuration %}
state_address:
description: KNX group address of the binary sensor. DPT 1
required: true
type: string
name:
description: A name for this device used within Home Assistant.
required: false
type: string
sync_state:
description: Actively read the value from the bus. If False
no GroupValueRead telegrams will be sent to the bus. sync_state
can be set to init
to just initialize state on startup, expire <minutes>
to read the state from the KNX bus when no telegram was received for <minutes> or every <minutes>
to update it regularly every <minutes>. Maximum value for <minutes> is 1440. If just a number is configured "expire"-behaviour is used. Defaults to True
which is interpreted as "expire 60".
required: false
type: [boolean, string, integer]
default: True
device_class:
description: Sets the class of the device, changing the device state and icon that is displayed on the frontend.
required: false
type: string
reset_after:
description: Reset back to OFF state after specified seconds.
required: false
type: float
invert:
description: Invert the telegrams payload before processing. This is applied before context_timeout
or reset_after
is evaluated.
required: false
type: boolean
default: False
ignore_internal_state:
description: Specifies if telegrams should ignore the internal state and always trigger a Home Assistant state update.
required: false
type: boolean
default: False
context_timeout:
description: The time in seconds between multiple identical telegram payloads would count towards the internal counter that is used for automations. Ex. You have automations in place that trigger your lights on button press and another set of lights if you click that button twice. This setting defines the time that a second button press would count toward, so if you set this 3.0 you can take up to 3 seconds in order to trigger the second button press. If set ignore_internal_state
will be set to True
internally. Maximum value is 10.0.
required: false
type: float
default: None
{% endconfiguration %}
Support for automations
You can use a built in event in order to trigger an automation (e.g. to switch on a light when a switch was pressed).
Let's pretend you have a binary sensor with the name Livingroom.Switch
and you want to switch one light on when the button was pressed once and two other lights when the button was pressed twice.
# Example automation.yaml entry
automation:
- trigger:
platform: numeric_state
entity_id: binary_sensor.Livingroom_Switch
attribute: counter
above: 0
below: 2
condition:
- condition: state
entity_id: binary_sensor.cover_abstell
state: 'on'
action:
- entity_id: light.hue_color_lamp_1
service: light.turn_on
- trigger:
platform: numeric_state
entity_id: binary_sensor.Livingroom_Switch
attribute: counter
above: 1
below: 3
condition:
- condition: state
entity_id: binary_sensor.cover_abstell
state: 'on'
action:
- entity_id: light.hue_bloom_1
service: homeassistant.turn_on
- entity_id: light.hue_bloom_2
service: homeassistant.turn_on
{% configuration %} name: description: A name for this device used within Home Assistant. required: false type: string counter: description: Set to 2 if your only want the action to be executed if the button was pressed twice. To 3 for three times button pressed. required: false type: integer default: 1 hook: description: Indicates if the automation should be executed on what state of the binary sensor. Values are "on" or "off". required: false type: string default: "on" action: description: Specify a list of actions analog to the automation rules. required: false type: list {% endconfiguration %}
Climate
The knx
climate platform is used as an interface to KNX thermostats and room controllers.
To use your KNX thermostats in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
climate:
- name: HASS-Kitchen.Temperature
temperature_address: '5/1/1'
setpoint_shift_address: '5/1/2'
setpoint_shift_state_address: '5/1/3'
target_temperature_state_address: '5/1/4'
operation_mode_address: '5/1/5'
operation_mode_state_address: '5/1/6'
Alternatively, if your device has dedicated binary group addresses for frost/night/comfort mode:
# Example configuration.yaml entry
knx:
climate:
- name: HASS-Kitchen.Temperature
temperature_address: '5/1/1'
setpoint_shift_address: '5/1/2'
setpoint_shift_state_address: '5/1/3'
target_temperature_state_address: '5/1/4'
operation_mode_frost_protection_address: '5/1/5'
operation_mode_night_address: '5/1/6'
operation_mode_comfort_address: '5/1/7'
operation_mode_state_address: '5/1/8'
If your device doesn't support setpoint_shift calculations (i.e., if you don't provide a setpoint_shift_address
value) please set the min_temp
and max_temp
attributes of the climate device to avoid issues with exceeding valid temperature values in the frontend. Please do also make sure to add the target_temperature_address
to the configuration in this case.:
# Example configuration.yaml entry
knx:
climate:
- name: HASS-Kitchen.Temperature
temperature_address: '5/1/2'
target_temperature_address: '5/1/4'
target_temperature_state_address: '5/1/1'
operation_mode_frost_protection_address: '5/1/5'
operation_mode_night_address: '5/1/6'
operation_mode_comfort_address: '5/1/7'
operation_mode_state_address: '5/1/8'
operation_mode_standby_address: '5/1/9'
min_temp: 7.0
max_temp: 32.0
setpoint_shift_mode
allows the two following DPTs to be used:
- DPT6002 (for 1 byte signed integer)
- DPT9002 (for 2 byte float)
Example:
# Example configuration.yaml entry
knx:
climate:
- name: HASS-Kitchen.Temperature
temperature_address: '5/1/1'
setpoint_shift_address: '5/1/2'
setpoint_shift_state_address: '5/1/3'
setpoint_shift_mode: 'DPT9002'
target_temperature_state_address: '5/1/4'
operation_mode_address: '5/1/5'
operation_mode_state_address: '5/1/6'
operation_mode_frost_protection_address
/ operation_mode_night_address
/ operation_mode_comfort_address
/ operation_mode_standby_address
are not necessary if operation_mode_address
is specified.
If the actor doesn't support explicit state communication objects the *_state_address can be configured with the same group address as the writeable *_address. The Read-Flag for the *_state_address communication object has to be set in ETS to support initial reading e.g., when starting Home Assistant.
The following values are valid for the heat_cool_address
and the heat_cool_state_address
:
- 0 (cooling)
- 1 (heating)
The following values are valid for the hvac_mode
attribute:
- Off (maps internally to HVAC_MODE_OFF within Home Assistant)
- Auto (maps internally to HVAC_MODE_AUTO within Home Assistant)
- Heat (maps internally to HVAC_MDOE_HEAT within Home Assistant)
- Cool (maps internally to HVAC_MDOE_COOL within Home Assistant)
- Fan only (maps internally to HVAC_MODE_FAN_ONLY within Home Assistant)
- Dry (maps internally to HVAC_MODE_DRY within Home Assistant)
The following presets are valid for the preset_mode
attribute:
- Auto (maps internally to PRESET_NONE within Home Assistant)
- Comfort (maps internally to PRESET_COMFORT within Home Assistant)
- Standby (maps internally to PRESET_AWAY within Home Assistant)
- Night (maps internally to PRESET_SLEEP within Home Assistant)
- Frost Protection (maps internally to PRESET_ECO within Home Assistant)
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
default: KNX Climate
type: string
temperature_address:
description: KNX group address for reading current room temperature from KNX bus. DPT 9.001
required: true
type: string
temperature_step:
description: Defines the step size in Kelvin for each step of setpoint_shift.
required: false
type: float
default: 0.1
target_temperature_address:
description: KNX group address for setting target temperature. DPT 9.001
required: false
type: string
target_temperature_state_address:
description: KNX group address for reading current target temperature from KNX bus. DPT 9.001
required: true
type: string
setpoint_shift_address:
description: KNX address for setpoint_shift. DPT 6.010 or 9.001 based on setpoint_shift_mode
required: false
type: string
setpoint_shift_state_address:
description: KNX address for reading setpoint_shift. DPT 6.010 or 9.001 based on setpoint_shift_mode
required: false
type: string
setpoint_shift_mode:
description: Defines the internal device DPT used.
required: false
default: 0.5
type: string
default: DPT6010
setpoint_shift_min:
description: Minimum value of setpoint shift.
required: false
default: -6
type: float
setpoint_shift_max:
description: Maximum value of setpoint shift.
required: false
default: 6
type: float
operation_mode_address:
description: KNX address for setting operation mode (Frost protection/night/comfort). DPT 20.102
required: false
type: string
operation_mode_state_address:
description: KNX address for reading operation mode. DPT 20.102
required: false
type: string
controller_status_address:
description: KNX address for HVAC controller status (in accordance with KNX AN 097/07 rev 3).
required: false
type: string
controller_status_state_address:
description: KNX address for reading HVAC controller status.
required: false
type: string
controller_mode_address:
description: KNX address for setting HVAC controller modes. DPT 20.105
required: false
type: string
controller_mode_state_address:
description: KNX address for reading HVAC Control Mode. DPT 20.105
required: false
type: string
heat_cool_address:
description: KNX address for switching between heat/cool mode. DPT 1.100
required: false
type: string
heat_cool_state_address:
description: KNX address for reading heat/cool mode. DPT 1.100
required: false
type: string
operation_mode_frost_protection_address:
description: KNX address for switching on/off frost/heat protection mode. DPT 1
required: false
type: string
operation_mode_night_address:
description: KNX address for switching on/off night mode. DPT 1
required: false
type: string
operation_mode_comfort_address:
description: KNX address for switching on/off comfort mode. DPT 1
required: false
type: string
operation_mode_standby_address:
description: KNX address for switching on/off standby mode. DPT 1
required: false
type: string
operation_modes:
description: Overrides the supported operation modes. Provide the supported preset_mode
values for your device.
required: false
type: list
controller_modes:
description: Overrides the supported controller modes. Provide the supported hvac_mode
values for your device.
required: false
type: list
on_off_address:
description: KNX address for switching the climate device on/off. DPT 1
required: false
type: string
on_off_invert:
description: Value for switching the climate device on/off is inverted.
required: false
default: false
type: boolean
on_off_state_address:
description: KNX address for gathering the current state (on/off) of the climate device. DPT 1
required: false
type: string
min_temp:
description: Override the minimum temperature.
required: false
type: float
max_temp:
description: Override the maximum temperature.
required: false
type: float
{% endconfiguration %}
Cover
The knx
cover platform is used as an interface to KNX covers.
To use your KNX covers in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
cover:
- name: "Kitchen.Shutter"
move_long_address: '3/0/0'
move_short_address: '3/0/1'
stop_address: '3/0/4'
position_address: '3/0/3'
position_state_address: '3/0/2'
travelling_time_down: 51
travelling_time_up: 61
{% configuration %} name: description: A name for this device used within Home Assistant. required: false default: KNX Cover type: string move_long_address: description: KNX group address for moving the cover full up or down. DPT 1 required: false type: string move_short_address: description: KNX group address for moving the cover short time up or down. DPT 1 required: false type: string stop_address: description: KNX group address for stopping the current movement from the cover. DPT 1 required: false type: string position_address: description: KNX group address for moving the cover to the dedicated position. DPT 5.001 required: false type: string position_state_address: description: Separate KNX group address for requesting the current position of the cover. DPT 5.001 required: false type: string angle_address: description: KNX group address for moving the cover to the dedicated angle. DPT 5.001 required: false type: string angle_state_address: description: Separate KNX group address for requesting the current angle of cover. DPT 5.001 required: false type: string travelling_time_down: description: Time cover needs to travel down in seconds. Needed to calculate the intermediate positions of cover while traveling. required: false default: 25 type: integer travelling_time_up: description: Time cover needs to travel up in seconds. Needed to calculate the intermediate positions of cover while traveling. required: false default: 25 type: integer invert_position: description: Set this to true if your actuator report fully closed as 0% in KNX. required: false default: false type: boolean invert_angle: description: Set this to true if your actuator reports tilt fully closed as 0% in KNX. required: false default: false type: boolean {% endconfiguration %}
Light
The knx light
integration is used as an interface to control KNX actuators for lighting applications such as:
- switching actuators
- dimming actuators
- LED controllers
- DALI gateways
Configuration
To use your KNX light in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
light:
- name: 'kitchen'
address: '1/0/9'
{% configuration %}
address:
description: KNX group address for switching the light on and off. DPT 1.001
required: true
type: string
state_address:
description: KNX group address for retrieving the switch state of the light. DPT 1.001
required: false
type: string
name:
description: A name for this device used within Home Assistant.
required: false
type: string
brightness_address:
description: KNX group address for setting the brightness of the light in percent (absolute dimming). DPT 5.001
required: false
type: string
brightness_state_address:
description: KNX group address for retrieving the brightness of the light in percent. DPT 5.001
required: false
type: string
color_address:
description: KNX group address for setting the RGB color of the light. DPT 232.600
required: false
type: string
color_state_address:
description: KNX group address for retrieving the RGB color of the light. DPT 232.600
required: false
type: string
rgbw_address:
description: KNX group address for setting the RGBW color of the light. DPT 251.600
required: false
type: string
rgbw_state_address:
description: KNX group address for retrieving the RGBW color of the light. DPT 251.600
required: false
type: string
color_temperature_address:
description: KNX group address for setting the color temperature of the light. DPT 5.001 or 7.600 based on color_temperature_mode
required: false
type: string
color_temperature_state_address:
description: KNX group address for retrieving the color temperature of the light. DPT 5.001 or 7.600 based on color_temperature_mode
required: false
type: string
color_temperature_mode:
description: Color temperature group address data type. absolute
color temperature in Kelvin. color_temperature_address -> DPT 7.600. relative
color temperature in percent cold white (0% warmest; 100% coldest). color_temperature_address -> DPT 5.001
required: false
type: string
default: absolute
min_kelvin:
description: Warmest possible color temperature in Kelvin. (Used in combination with color_temperature_address)
required: false
type: integer
default: 2700
max_kelvin:
description: Coldest possible color temperature in Kelvin. (Used in combination with color_temperature_address)
required: false
type: integer
default: 6000
{% endconfiguration %}
Many KNX devices can change their state internally without a message to the switch address on the KNX bus, e.g., if you configure a scene or a timer on a channel. The optional state_address
can be used to inform Home Assistant about these state changes. If a KNX message is seen on the bus addressed to the given state_address
(in most cases from the light actuator), it will overwrite the state of the switch object.
For switching/light actuators that are only controlled by a single group address and don't have dedicated state communication objects you can set state_address
to the same value as address
.
Note on tunable white: Home Assistant uses Mireds as the unit for color temperature, whereas KNX typically uses Kelvin. The Kelvin/Mireds relationship is reciprocal, not linear, therefore the color temperature pickers (sliders) in Home Assistant may not align with ones of KNX visualizations. This is the expected behavior.
Extended configuration example
knx:
light:
# dimmable light
- name: Bedroom-Light-1
address: '1/0/9'
state_address: '1/1/9'
brightness_address: '1/2/9'
brightness_state_address: '1/3/9'
#
# RGB light
- name: Bathroom-Light-1
address: '1/0/9'
state_address: '1/1/9'
brightness_address: '1/2/9'
brightness_state_address: '1/3/9'
color_address: '1/4/9'
color_state_address: '1/5/9'
#
# tunable white light
- name: Office-Light-1
address: '1/0/21'
state_address: '1/1/21'
brightness_address: '1/2/21'
brightness_state_address: '1/3/21'
color_temperature_address: '1/4/21'
color_temperature_state_address: '1/5/21'
color_temperature_mode: absolute
min_kelvin: 2550
max_kelvin: 6200
#
# actuator without dedicated state communication object
- name: Cellar-Light-1
address: '1/0/5'
state_address: '1/0/5'
Notify
The knx
notify platform allows you to send notifications to KNX devices.
Configuration
To use your KNX switch in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
knx:
notify:
- name: Alarm
address: '5/1/10'
{% configuration %}
address:
description: KNX group address of the notification. DPT 16.000
required: true
type: string
name:
description: A name for this device used within Home Assistant.
required: false
type: string
{% endconfiguration %}
The knx
scenes platform allows you to trigger KNX scenes.
Scene
Configuration
To use your KNX scene in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
scene:
- name: Romantic
address: 8/8/8
scene_number: 23
{% configuration %} address: description: KNX group address for the scene. DPT 17.001 required: true type: string scene_number: description: KNX scene number to be activated. ( 1 ... 64 ) required: true type: integer name: description: A name for this device used within Home Assistant. required: false type: string {% endconfiguration %}
Sensor
The knx
sensor platform allows you to monitor KNX sensors.
Sensors are read-only. To write to the knx-bus configure an exposure KNX Integration - Expose.
Configuration
To use your KNX sensor in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
sensor:
- name: Heating.Valve1
state_address: '2/0/0'
In order to actively read the sensor data from the bus all 30 seconds you can add the following lines to your configuration.yaml
:
# Example configuration.yaml entry
knx:
sensor:
- name: Heating.Valve1
state_address: '2/0/0'
sync_state: expire 30
{% configuration %}
state_address:
description: KNX group address of the sensor.
required: true
type: string
name:
description: A name for this device used within Home Assistant.
required: false
type: string
sync_state:
description: Actively read the value from the bus. If False
no GroupValueRead telegrams will be sent to the bus. sync_state
can be set to init
to just initialize state on startup, expire <minutes>
to read the state from the KNX bus when no telegram was received for <minutes> or every <minutes>
to update it regularly every <minutes>. Maximum value for <minutes> is 1440. If just a number is configured "expire"-behaviour is used. Defaults to True
which is interpreted as "expire 60".
required: false
type: [boolean, string, integer]
default: True
type:
description: A type from the following table must be defined. The DPT of the group address should match the expected KNX DPT to be parsed correctly.
required: true
type: string
always_callback:
description: Defines if telegrams with equal payload as the previously received telegram should trigger a state update within Home Assistant.
required: false
type: boolean
default: False
{% endconfiguration %}
KNX DPT | type | size in byte | range | unit |
---|---|---|---|---|
5.001 | percent | 1 | 0 ... 100 | % |
5.003 | angle | 1 | 0 ... 360 | ° |
5.004 | percentU8 | 1 | 0 ... 255 | % |
5.010 | pulse | 1 | 0 ... 255 | |
5.010 | 1byte_unsigned | 1 | 0 ... 255 | |
6.001 | percentV8 | 1 | -128 ... 127 | % |
6.010 | counter_pulses | 1 | -128 ... 127 | counter pulses |
7.001 | 2byte_unsigned | 2 | 0 ... 65535 | pulses |
7.002 | time_period_msec | 2 | 0 ... 65535 | ms |
7.003 | time_period_10msec | 2 | 0 ... 65535 | ms |
7.004 | time_period_100msec | 2 | 0 ... 65535 | ms |
7.005 | time_period_sec | 2 | 0 ... 65535 | s |
7.006 | time_period_min | 2 | 0 ... 65535 | min |
7.007 | time_period_hrs | 2 | 0 ... 65535 | h |
7.011 | length_mm | 2 | 0 ... 65535 | mm |
7.012 | current | 2 | 0 ... 65535 | mA |
7.013 | brightness | 2 | 0 ... 65535 | lx |
7.600 | color_temperature | 2 | 0 ... 65535 | K |
8.001 | 2byte_signed | 2 | -32768 ... 32767 | pulses |
8.002 | delta_time_ms | 2 | -32768 ... 32767 | ms |
8.005 | delta_time_sec | 2 | -32768 ... 32767 | s |
8.006 | delta_time_min | 2 | -32768 ... 32767 | min |
8.007 | delta_time_hrs | 2 | -32768 ... 32767 | h |
8.010 | percentV16 | 2 | -32768 ... 32767 | % |
8.011 | rotation_angle | 2 | -32768 ... 32767 | ° |
9.* | enthalpy | 2 | -671088.64 ... 670760.96 | H |
9.001 | temperature | 2 | -273 ... 670760 | °C |
9.002 | temperature_difference_2byte | 2 | -670760 ... 670760 | K |
9.003 | temperature_a | 2 | -670760 ... 670760 | K/h |
9.004 | illuminance | 2 | 0 ... 670760 | lx |
9.005 | wind_speed_ms | 2 | 0 ... 670760 | m/s |
9.006 | pressure_2byte | 2 | 0 ... 670760 | Pa |
9.007 | humidity | 2 | 0 ... 670760 | % |
9.008 | ppm | 2 | -671088.64 ... 670760.96 | ppm |
9.010 | time_1 | 2 | -670760 ... 670760 | s |
9.011 | time_2 | 2 | -670760 ... 670760 | ms |
9.020 | voltage | 2 | -671088.64 ... 670760.96 | mV |
9.022 | power_density | 2 | -671088.64 ... 670760.96 | W/m² |
9.023 | kelvin_per_percent | 2 | -671088.64 ... 670760.96 | K/% |
9.024 | power_2byte | 2 | -671088.64 ... 670760.96 | kW |
9.025 | volume_flow | 2 | -671088.64 ... 670760.96 | l/h |
9.026 | rain_amount | 2 | -671088.64 ... 670760.96 | l/m² |
9.027 | temperature_f | 2 | -459.6 ... 670760 | °F |
9.028 | wind_speed_kmh | 2 | 0 ... 670760 | km/h |
12.*** | 4byte_unsigned | 4 | 0 ... 4294967295 | |
13.*** | 4byte_signed | 4 | -2147483648 ... 2147483647 | |
13.002 | flow_rate_m3h | 4 | -2147483648 ... 2147483647 | m³/h |
13.010 | active_energy | 4 | -2147483648 ... 2147483647 | Wh |
13.011 | apparant_energy | 4 | -2147483648 ... 2147483647 | VAh |
13.012 | reactive_energy | 4 | -2147483648 ... 2147483647 | VARh |
13.013 | active_energy_kwh | 4 | -2147483648 ... 2147483647 | kWh |
13.014 | apparant_energy_kvah | 4 | -2147483648 ... 2147483647 | kVAh |
13.015 | reactive_energy_kvarh | 4 | -2147483648 ... 2147483647 | kVARh |
13.100 | long_delta_timesec | 4 | -2147483648 ... 2147483647 | s |
14.000 | acceleration | 4 | m/s² | |
14.*** | 4byte_float | 4 | ||
14.001 | acceleration_angular | 4 | rad/s² | |
14.002 | activation_energy | 4 | J/mol | |
14.003 | activity | 4 | s⁻¹ | |
14.004 | mol | 4 | mol | |
14.005 | amplitude | 4 | ||
14.006 | angle_rad | 4 | rad | |
14.007 | angle_deg | 4 | ° | |
14.008 | angular_momentum | 4 | J s | |
14.009 | angular_velocity | 4 | rad/s | |
14.010 | area | 4 | m² | |
14.011 | capacitance | 4 | F | |
14.012 | charge_density_surface | 4 | C/m² | |
14.013 | charge_density_volume | 4 | C/m³ | |
14.014 | compressibility | 4 | m²/N | |
14.015 | conductance | 4 | S | |
14.016 | electrical_conductivity | 4 | S/m | |
14.017 | density | 4 | kg/m³ | |
14.018 | electric_charge | 4 | C | |
14.019 | electric_current | 4 | A | |
14.020 | electric_current_density | 4 | A/m² | |
14.021 | electric_dipole_moment | 4 | C m | |
14.022 | electric_displacement | 4 | C/m² | |
14.023 | electric_field_strength | 4 | V/m | |
14.024 | electric_flux | 4 | c | |
14.025 | electric_flux_density | 4 | C/m² | |
14.026 | electric_polarization | 4 | C/m² | |
14.027 | electric_potential | 4 | V | |
14.028 | electric_potential_difference | 4 | V | |
14.029 | electromagnetic_moment | 4 | A m² | |
14.030 | electromotive_force | 4 | V | |
14.031 | energy | 4 | J | |
14.032 | force | 4 | N | |
14.033 | frequency | 4 | Hz | |
14.034 | angular_frequency | 4 | rad/s | |
14.035 | heatcapacity | 4 | J/K | |
14.036 | heatflowrate | 4 | W | |
14.037 | heat_quantity | 4 | J | |
14.038 | impedance | 4 | Ω | |
14.039 | length | 4 | m | |
14.040 | light_quantity | 4 | lm s | |
14.041 | luminance | 4 | cd/m² | |
14.042 | luminous_flux | 4 | lm | |
14.043 | luminous_intensity | 4 | cd | |
14.044 | magnetic_field_strength | 4 | A/m | |
14.045 | magnetic_flux | 4 | Wb | |
14.046 | magnetic_flux_density | 4 | T | |
14.047 | magnetic_moment | 4 | A m² | |
14.048 | magnetic_polarization | 4 | T | |
14.049 | magnetization | 4 | A/m | |
14.050 | magnetomotive_force | 4 | A | |
14.051 | mass | 4 | kg | |
14.052 | mass_flux | 4 | kg/s | |
14.053 | momentum | 4 | N/s | |
14.054 | phaseanglerad | 4 | rad | |
14.055 | phaseangledeg | 4 | ° | |
14.056 | power | 4 | W | |
14.057 | powerfactor | 4 | cosΦ | |
14.058 | pressure | 4 | Pa | |
14.059 | reactance | 4 | Ω | |
14.060 | resistance | 4 | Ω | |
14.061 | resistivity | 4 | Ω m | |
14.062 | self_inductance | 4 | H | |
14.063 | solid_angle | 4 | sr | |
14.064 | sound_intensity | 4 | W/m² | |
14.065 | speed | 4 | m/s | |
14.066 | stress | 4 | Pa | |
14.067 | surface_tension | 4 | N/m | |
14.068 | common_temperature | 4 | °C | |
14.069 | absolute_temperature | 4 | K | |
14.070 | temperature_difference | 4 | K | |
14.071 | thermal_capacity | 4 | J/K | |
14.072 | thermal_conductivity | 4 | W/mK | |
14.073 | thermoelectric_power | 4 | V/K | |
14.074 | time_seconds | 4 | s | |
14.075 | torque | 4 | N m | |
14.076 | volume | 4 | m³ | |
14.077 | volume_flux | 4 | m³/s | |
14.078 | weight | 4 | N | |
14.079 | work | 4 | J | |
16.000 | string | 14 | ||
17.001 | scene_number | 1 | 1 ... 64 |
Full example
# Example configuration.yaml entry
knx:
sensor:
- name: Heating.Valve1
state_address: '2/0/0'
sync_state: init
type: 'percent'
- name: Kitchen.Temperature
state_address: '6/2/1'
sync_state: every 60
type: 'temperature'
Switch
The knx
switch platform is used as an interface to switching actuators.
Configuration
To use your KNX switch in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
knx:
switch:
- name: Kitchen.Coffee
address: '1/1/6'
{% configuration %}
address:
description: KNX group address for switching the switch on/off. DPT 1
required: true
type: string
name:
description: A name for this device used within Home Assistant.
required: false
default: KNX Switch
type: string
state_address:
description: Separate KNX group address for retrieving the switch state. DPT 1
required: false
type: string
invert:
description: Invert the telegrams payload before processing or sending. This is applied before reset_after
is evaluated so the reset will send "1" to the bus.
required: false
type: boolean
default: False
reset_after:
description: Reset the switch back to OFF after specified seconds.
required: false
type: float
{% endconfiguration %}
Some KNX devices can change their state internally without any messages on the KNX bus, e.g., if you configure a timer on a channel. The optional state_address
can be used to inform Home Assistant about these state changes. If a KNX message is seen on the bus addressed to the given state address, this will overwrite the state of the switch object.
For switching actuators that are only controlled by a single group address and can't change their state internally, you don't have to configure the state address.
Weather
The knx
weather platform is used as an interface to KNX weather stations.
To use your KNX weather station in your installation, add the following lines to your top level KNX Integration configuration key in configuration.yaml
:
# Example configuration.yaml entry
knx:
weather:
- name: "home"
address_temperature: "7/0/0"
address_brightness_south: "7/0/1"
address_brightness_west: "7/0/2"
address_brightness_east: "7/0/3"
address_brightness_north: "7/0/11"
address_wind_speed: "7/0/4"
address_rain_alarm: "7/0/5"
address_frost_alarm: "7/0/6"
address_wind_alarm: "7/0/7"
address_day_night: "7/0/8"
address_air_pressure: "7/0/9"
address_humidity: "7/0/10"
expose_sensors: False
sync_state: True
{% configuration %}
name:
description: A name for this device used within Home Assistant.
required: false
default: KNX Weather
type: string
address_temperature:
description: KNX group address for reading current outside temperature from KNX bus. DPT 9.001
required: true
type: string
address_brightness_south:
description: KNX group address for reading current brightness to south coordinate from KNX bus. DPT 9.004
required: false
type: string
address_brightness_west:
description: KNX group address for reading current brightness to west coordinate from KNX bus. DPT 9.004
required: false
type: string
address_brightness_east:
description: KNX group address for reading current brightness to east coordinate from KNX bus. DPT 9.004
required: false
type: string
address_brightness_north:
description: KNX group address for reading current brightness to north coordinate from KNX bus. DPT 9.004
required: false
type: string
address_wind_speed:
description: KNX group address for reading current wind speed from KNX bus. DPT 9.005
required: false
type: string
address_rain_alarm:
description: KNX group address for reading if rain alarm is on/off.
required: false
type: string
address_frost_alarm:
description: KNX group address for reading if frost alarm is on/off.
required: false
type: string
address_wind_alarm:
description: KNX group address for reading if wind alarm is on/off.
required: false
type: string
address_day_night:
description: KNX group address for reading if it's day/night.
required: false
type: string
address_air_pressure:
description: KNX address reading current air pressure. DPT 9.006
required: false
type: string
address_humidity:
description: KNX address for reading current humidity. DPT 9.007
required: false
type: string
expose_sensors:
description: If true, exposes all sensor values as dedicated sensors to HA.
required: false
type: boolean
default: False
sync_state:
description: Actively read the value from the bus. If False
no GroupValueRead telegrams will be sent to the bus.
required: false
type: boolean
default: True
{% endconfiguration %}